kW to kVA and kVA to kW Calculator
Result
For guidance only. The real power factor changes with the load, so use the value from your load data or meter. For three phase current, the line-to-line voltage is used. Verify with the applicable code and your project specification.
How the formula works
In an AC circuit there are three kinds of power. Real power (kW) does the useful work. Apparent power (kVA) is what the supply, cables, transformers and generators must carry. Reactive power (kVAR) is the part that moves back and forth and does no work. The power factor links real and apparent power.
1. kW to kVA
kVA = kW / power factor
2. kVA to kW
kW = kVA x power factor
3. Reactive power and angle
kVAR = square root of (kVA x kVA – kW x kW)
Power factor angle = arccos(power factor)
4. Current (optional)
Single phase: I = kVA x 1000 / V
Three phase: I = kVA x 1000 / (1.732 x V), where V is the line-to-line voltage
5. kW to HP
HP = kW / 0.746
Where
- kW = real (active) power, kVA = apparent power, kVAR = reactive power
- Power factor = kW / kVA, a number from 0 to 1
- 1 MW = 1000 kW and 1 kW = 1000 W (the same for MVA, kVA and VA)
Typical power factor values
- Resistive loads such as heaters and incandescent lamps: about 1.0
- Induction motors at full load: about 0.8 to 0.9, and lower at light load
- Offices and commercial buildings: about 0.85 to 0.95
- Lightly loaded motors and old fluorescent lighting without correction: about 0.6 to 0.7
- Many utilities ask for at least 0.9 to 0.95 and may charge a penalty below that. The local rule is final.
How to use the calculator
- Select kW to kVA or kVA to kW, and the power unit.
- Enter the power and select the power factor. Choose Custom if you know the exact value.
- Optionally select single or three phase and the voltage to get the current.
- Click Calculate, then Download PDF Result if you need a record.
Important notes
- The power factor changes with the load. Use a value from your load data, the motor nameplate or a meter reading, not a guess.
- Generators, transformers and UPS systems are rated in kVA, while loads such as motors are often given in kW. Convert carefully with the right power factor.
- Three phase current uses the line-to-line voltage, such as 415 V.
Worked example
Example 1 – kW to kVA with current
Load 100 kW, power factor 0.8, three phase 415 V.
kVA = 100 / 0.8 = 125 kVA
kVAR = square root of (125 x 125 – 100 x 100) = 75 kVAR
Angle = arccos(0.8) = 36.87 degrees
Current = 125 x 1000 / (1.732 x 415) = 173.9 A
Example 2 – kVA to kW for a transformer
Transformer 500 kVA, power factor 0.9, three phase 415 V.
kW = 500 x 0.9 = 450 kW
kVAR = 217.9 kVAR, angle 25.84 degrees
Full load current = 500 x 1000 / (1.732 x 415) = 695.6 A
Example 3 – MVA to kW at medium voltage
2 MVA, power factor 0.85, three phase 11,000 V.
kW = 2000 x 0.85 = 1700 kW
Current = 2000 x 1000 / (1.732 x 11000) = 104.97 A
Example 4 – Small single phase UPS
UPS 5000 VA, power factor 0.8, single phase 230 V.
kW = 5 x 0.8 = 4 kW (4000 W)
Current = 5 x 1000 / 230 = 21.74 A
Common mistakes
- Assuming kW and kVA are the same. They are equal only when the power factor is 1.0.
- Using the wrong power factor. A guessed value can make a generator or transformer too small or too large.
- Dividing instead of multiplying. kVA = kW / power factor, but kW = kVA x power factor.
- Sizing a generator on kW only. A generator is rated in kVA and also has a rated power factor, usually 0.8.
- Using the phase voltage in the three phase current formula. Use the line-to-line voltage, such as 415 V.
- Forgetting that motor power factor drops at part load. A lightly loaded motor has a poor power factor.
- Mixing units. Check whether you are using W, kW or MW before you enter the power.
- Confusing kW with HP. 1 HP is 0.746 kW, and motor ratings in HP are mechanical output, not electrical input.
- Ignoring the utility power factor rules. A low power factor can bring penalties on the bill even when the kW is small.
Frequently asked questions
What is the difference between kW and kVA?
kW is real power that does useful work. kVA is apparent power, the total power the supply has to deliver. kVA is always equal to or greater than kW.
How do I convert kW to kVA?
Divide kW by the power factor. For example, 100 kW at a power factor of 0.8 is 125 kVA.
How do I convert kVA to kW?
Multiply kVA by the power factor. For example, 500 kVA at 0.9 is 450 kW.
What is the power factor?
It is the ratio of real power to apparent power (kW / kVA). A power factor of 1.0 means all the power is used for work. A lower value means part of it is reactive power.
What power factor should I use?
Use the value from your load data or meter. As typical values, about 0.8 for a generator rating, about 0.85 to 0.9 for motor loads, and 1.0 for heaters.
What is kVAR?
kVAR is reactive power. It is needed by motors and transformers to build magnetic fields, but it does no useful work. kVAR = square root of (kVA squared – kW squared).
Why are generators and transformers rated in kVA?
Their heating depends on the current, and the current depends on kVA, not on kW. The same equipment must be able to carry the current for any power factor.
How do I find the current from kVA?
For three phase: I = kVA x 1000 / (1.732 x V). For single phase: I = kVA x 1000 / V. The calculator gives this if you select the supply system and the voltage.
What is the kVA of a 100 kW load?
It depends on the power factor. At 1.0 it is 100 kVA, at 0.9 it is 111.1 kVA, and at 0.8 it is 125 kVA.
How can I improve a low power factor?
Install capacitors (power factor correction) close to the load or at the main panel. This reduces kVAR and kVA, and lowers the current and the losses.
Does a low power factor increase the electricity bill?
In many places yes. Utilities charge for kVA demand or add a penalty when the power factor is below a limit such as 0.9 or 0.95. Check your tariff.
Is this calculator a replacement for a load calculation?
No. It converts between kW and kVA for a given power factor. Equipment selection needs a full load list, diversity and the manufacturer data.