🚨 Detector Count Calculator
Find how many smoke or heat detectors a room needs from its size and ceiling height, using typical NFPA 72 and IS 2189 spacing.
Open calculator
MEP AnalysisFree · No signup · Formula shown with every resultFree fire and safety calculators for sprinkler flow, fire pumps, water tanks, detectors and alarm batteries. Each tool explains its formula and gives you a PDF result.
Standard-based tools with a PDF result. Free to use, no signup.
Find how many smoke or heat detectors a room needs from its size and ceiling height, using typical NFPA 72 and IS 2189 spacing.
Open calculatorCalculate the battery capacity (Ah) for a fire alarm system from standby and alarm currents, with a downloadable PDF result.
Open calculatorCalculate friction loss, velocity, required pipe size or maximum flow for fire sprinkler and hydrant pipes using the Hazen-Williams formula.
Open calculatorSize a fire pump from hazard class, pipe friction and height: get design flow, total head, standard pump rating and motor kW with a PDF result.
Open calculatorCalculate the fire water tank capacity for sprinkler and hydrant systems from hazard class, flow and duration, and check an existing tank. Also gives the suggested fire pump rating.
Open calculatorCalculate sprinkler design flow, operating heads, heads per room and K-factor pressure using typical NFPA 13 density and area values.
Open calculatorFire protection is about having enough water, pressure and warning time when something goes wrong. Systems are sized for the hazard in the building, so the figures that work for a small office are not the figures for a warehouse or a hospital. The fire and safety calculators on this page help you check the main quantities: storage, flow, pressure loss, pump power, detector count and alarm battery capacity.
Each tool shows its formula and the assumptions behind it. The example values on this page are illustrative. The flow rates, durations and spacing that you must actually use are set by the fire code, the hazard class of the building and the local fire authority.
Use the calculators for early sizing and for checking a design by hand. Final fire protection design must be prepared and approved according to the code and the authority that governs your project.
Every calculator explains the formula behind the result and lists common mistakes, so you can verify the answer instead of trusting a black box. Results are for estimation and learning, so always confirm final designs against the applicable code and with a qualified engineer.
The result of one step usually becomes the input of the next. This is a practical order to follow when you check a design.
These short examples show the arithmetic behind the tools. The numbers are illustrative, so replace them with your own project values.
A hydrant system is designed for 2,280 L/min for 60 minutes. These figures are only an example, so use the flow and duration your code requires.
Volume = 2,280 × 60= 136,800 L≈ 136.8 m³ of fire water storage
Water flows at 2,280 L/min through 100 m of 150 mm pipe with a Hazen-Williams C factor of 120.
p = 6.05 × 10⁵ × Q¹·⁸⁵ ÷ (C¹·⁸⁵ × d⁴·⁸⁷) bar per metre≈ 0.0035 bar/m × 100 m≈ 0.35 bar, which is about 3.6 m of head, over 100 m of pipe
A pump delivers 136.8 m³/h (2,280 L/min) against a total head of 70 m and has an efficiency of 65%.
Hydraulic kW = 9.81 × (136.8 ÷ 3600) × 70 = 26.1 kWShaft kW = 26.1 ÷ 0.65≈ 40 kW at the pump shaft, before choosing a standard motor
A 600 m² floor is covered by smoke detectors, and each detector is assumed to cover 60 m². Real spacing depends on the code, the ceiling height and the layout.
Detectors = 600 ÷ 6010 detectors as a first estimate, adjusted to the actual room layout
The panel draws 0.5 A in standby for 24 hours and 2 A in alarm for 0.5 hour. A 25% margin is added for battery ageing.
Capacity = 0.5 × 24 + 2 × 0.5 = 13 AhWith margin = 13 × 1.25≈ 16.3 Ah, so choose the next standard battery size
Most calculation errors come from small habits, not from hard formulas.
Short definitions of the terms you will meet in these calculators.
Quick answers about the Fire & Safety calculators.
Yes. All calculators on this page are free to use and do not need a signup or login.
Yes. Each calculator explains the formula behind the result, with a worked example and a list of common mistakes.
Multiply the required flow by the required duration, then add any extra reserve the code asks for. The flow and duration depend on the hazard class and the standard.
The jockey pump is small and holds the system pressure, so it covers leaks and small drops. The main fire pump starts when the pressure falls further or when water is drawn.
So that the fire reserve is always available and is not used up by normal daily demand.
It depends on the area, the detector type, the ceiling height and the spacing allowed by the code. Dividing area by coverage gives a first estimate only.
The system must stay alive during a power failure and still have enough power to sound the alarm. Standards usually specify the standby and alarm durations.
No. They help with estimates and checks, while the final design must follow the code and be approved by the authority.