Free · No signup · Formula shown with every result

Plumbing Calculators

Free plumbing and water calculators for pipe sizing, pump head, tank volume and daily demand. Each tool explains its formula and gives you a PDF result.

8Live calculators
100%Free, no signup
PDFOne-click download

All Plumbing Calculators

Standard-based tools with a PDF result. Free to use, no signup.

8
Plumbing

🕳️ Borewell Pump HP Calculator

Find the right borewell pump HP from water level, delivery height, flow and efficiency, with motor current and a downloadable PDF result.

Open calculator
Plumbing

🚿 Daily Water Demand Calculator

Estimate the daily water demand of a building from occupancy, landscaping and losses, with domestic and flushing split and storage volume.

Open calculator
Plumbing

🔧 Pipe Sizing Calculator

Find the pipe diameter and standard size for a water flow and design velocity, or check the velocity and flow of an existing pipe.

Open calculator
Plumbing

⛲ Pump Head (TDH) and Pump Power Calculator

Calculate the total dynamic head (TDH) of a pump from flow, pipe size, length and levels, and find the pump shaft power and the motor size.

Open calculator
Plumbing

♻️ STP Size Calculator

Find the sewage treatment plant (STP) size in KLD from building occupancy, with peak flow, reactor volume and equalization tank volume.

Open calculator
Plumbing

🛢️ Water Tank Filling Time Calculator

Find how long a water tank takes to fill, or the flow needed to fill it in a set time, with outflow, partial levels and a PDF result.

Open calculator
Plumbing

🛢️ Water Tank Size Calculator (OHT and Underground)

Find the size of an overhead tank (OHT) or underground tank from daily water demand, or find the capacity of a rectangular or cylindrical tank from its dimensions.

Open calculator
Plumbing

🏭 WTP Size Calculator

Find the water treatment plant (WTP) size from building occupancy, with raw water flow, filter diameter, raw water tank volume and chlorine need.

Open calculator
No match. Try a different word.

About Plumbing Calculators

Plumbing and water systems work only when flow, pipe size, pressure and storage agree with each other. A pipe that is too small makes noise and loses pressure, a pump that is too large wastes energy, and a tank that is too small runs dry at the wrong time. The plumbing calculators on this page help you check these links step by step.

The tools cover daily water demand, tank and treatment plant sizing, pipe sizing, pump head and power, and borewell pump selection. Each one shows its formula so you can see how flow, head and efficiency combine into the final figure.

Water demand figures differ between building types and between codes, so treat the example values as a starting point and confirm them against the standard or local authority requirements that apply to your project.

Every calculator explains the formula behind the result and lists common mistakes, so you can verify the answer instead of trusting a black box. Results are for estimation and learning, so always confirm final designs against the applicable code and with a qualified engineer.

How Plumbing calculations fit together

The result of one step usually becomes the input of the next. This is a practical order to follow when you check a design.

  1. Estimate the daily demand. Multiply the number of users by the water use per person per day, then add any other uses such as cooling or landscaping.
  2. Size the storage. Decide how many hours or days of storage you want and split it between underground and overhead tanks as the design needs.
  3. Size the pipes. Choose a pipe diameter from the flow and a sensible velocity, then check the pressure loss over the length.
  4. Find the pump head. Add the static lift, the friction losses and the pressure needed at the outlet to get the total dynamic head.
  5. Calculate the pump power. Convert flow and head into hydraulic power, then divide by the pump efficiency for the power at the shaft.
  6. Size the treatment plant. Use the expected sewage or water flow for the building to choose the capacity of the STP or WTP.

Worked Plumbing examples you can verify by hand

These short examples show the arithmetic behind the tools. The numbers are illustrative, so replace them with your own project values.

Daily demand and sewage flow

A block has 120 residents and the design figure is 135 litres per person per day. Many designers take about 80% of the water supplied as sewage, but confirm the ratio for your project.

Demand = 120 × 135 = 16,200 L per daySewage ≈ 16,200 × 0.8

16.2 m³ per day of demand and about 13 m³ per day of sewage to treat

Pipe diameter from flow and velocity

A line carries 10 m³/h and you want a velocity of about 1.5 m/s.

Area = Q ÷ v = (10 ÷ 3600) ÷ 1.5 = 0.00185 m²d = √(4 × A ÷ π)

≈ 48.6 mm internal diameter, so pick the next available pipe size

Pump power for a transfer pump

A pump moves 20 m³/h against a total head of 30 m and has an efficiency of 55%.

Hydraulic kW = 9.81 × (20 ÷ 3600) × 30 = 1.64 kWShaft kW = 1.64 ÷ 0.55

≈ 3.0 kW at the pump shaft, before choosing a standard motor

Borewell pump rating

A borewell pump lifts 5 m³/h from an effective head of 60 m at an efficiency of 45%. One kW is about 1.341 HP.

Hydraulic kW = 9.81 × (5 ÷ 3600) × 60 = 0.82 kWShaft kW = 0.82 ÷ 0.45 = 1.82 kW

≈ 2.4 HP at the shaft, so a 3 HP pump would be a reasonable first choice

Common mistakes to avoid

Most calculation errors come from small habits, not from hard formulas.

  • Using the nominal pipe size as the inside diameter.The inside diameter is what carries the water and it is usually smaller than the nominal size.
  • Leaving out friction losses and fittings.Pump head is more than the height of the tank. Pipe length, bends and valves add to it.
  • Sizing the tank on daily demand alone.Fire reserve and the hours when the supply is off also affect the storage you need.
  • Mixing flow units.Litres per second, litres per minute and cubic metres per hour are easy to confuse.
  • Ignoring suction conditions.A pump placed too high above the water level may not prime or may cavitate.
  • Forgetting the water table in a borewell.The water level drops while pumping, so the real head is higher than the depth to the static level.

Plumbing terms in plain words

Short definitions of the terms you will meet in these calculators.

LPCD
Litres per capita per day, the water use assumed for one person.
TDH
Total dynamic head, the static lift plus friction loss plus the pressure needed at the outlet.
Velocity
How fast water moves in a pipe. Very high velocity causes noise and pressure loss.
Static head
The vertical height the water has to be lifted.
Friction loss
Pressure lost because of rubbing against the pipe wall and fittings.
Hydraulic power
The power delivered to the water, equal to flow × head × gravity × density.
STP and WTP
Sewage treatment plant and water treatment plant.
Drawdown
The fall in water level in a well or borewell while it is being pumped.

Frequently asked questions

Quick answers about the Plumbing calculators.

Are the Plumbing calculators free?

Yes. All calculators on this page are free to use and do not need a signup or login.

Do the calculators show the formula?

Yes. Each calculator explains the formula behind the result, with a worked example and a list of common mistakes.

How much water does one person use per day?

It depends on the building type and the local code. A figure of 135 litres per person per day is commonly used for residential estimates in India, but you should confirm it for your project.

What pipe velocity should I design for?

Many designers keep water velocity within about 1 to 2 m/s. The right value depends on the service, the noise limit and the code.

Why is the pump power larger than the hydraulic power?

No pump is perfectly efficient. The power at the shaft equals the hydraulic power divided by the pump efficiency, and the motor must supply it.

How do I size a water tank?

Start from the daily demand, choose the hours or days of storage you need, then add any fire or other reserve required by the code.

How large should an STP be compared with the water supplied?

The plant is sized for the sewage flow, which is usually a large share of the water supplied. The exact ratio depends on the building and the code.

How do I choose a borewell pump HP?

Find the flow you need and the total head from the pumping water level, calculate the shaft power using the pump efficiency, then choose the next standard rating.

Can I use the results for final design?

The results are for estimation and learning. Please verify them against the applicable code and with a qualified engineer before final design or construction.

Looking for another calculator?

Browse every MEP calculator in one place, enter your values and get a clear, explained result.

⚡ View all calculators