Cable Size Calculator
Result
For guidance only. Current ratings are typical values for low-voltage multicore cables (IEC 60364-5-52 style, three loaded conductors). Verify with the cable manufacturer data, the applicable code (IEC / NEC / IS) and your project specification. Short-circuit rating and motor starting are not checked.
How the formula works
A cable must satisfy two conditions. First, it must carry the load current without overheating, which is its current capacity after derating. Second, the voltage lost along its length must stay within the allowed limit. This calculator checks both and selects the larger of the two sizes.
1. Load current
Three-phase: I = P / (square root of 3 x V x power factor x efficiency)
Single-phase: I = P / (V x power factor x efficiency)
If the load is given in kVA, I = kVA x 1000 / (square root of 3 x V) for three-phase. If the load is given in amps, it is used directly. A design margin is then added.
2. Derating
Rating needed from the table = I / (temperature factor x grouping factor x number of parallel cables)
Temperature factor = square root of ((max conductor temperature – ambient temperature) / (max conductor temperature – reference temperature))
The reference temperature is 30 deg C in air and 20 deg C in ground. The maximum conductor temperature is 70 deg C for PVC and 90 deg C for XLPE.
3. Voltage drop
Voltage drop = factor x I x L x (R x cos phi + X x sin phi)
The factor is the square root of 3 for three-phase and 2 for single-phase. L is the one-way length in km, R is the conductor resistance in ohm per km at the maximum operating temperature, and X is the reactance (about 0.08 ohm per km).
Voltage drop (%) = voltage drop / system voltage x 100
4. Selected size
The selected size is the larger of the smallest size that carries the current and the smallest size that meets the voltage drop limit.
5. Maximum length
Max length = allowed voltage drop / (factor x I x (R x cos phi + X x sin phi))
6. Current capacity of a known cable
Iz = tabulated rating x temperature factor x grouping factor x number of parallel cables
Maximum kVA = square root of 3 x V x Iz / 1000 (three-phase) or V x Iz / 1000 (single-phase). Maximum kW = kVA x power factor.
Typical values used
- Current ratings: typical values for multicore cables with three loaded conductors, in air clipped on a wall or tray, and buried directly in ground (IEC 60364-5-52 style). Single-phase circuits use the same ratings, which is slightly conservative.
- Grouping factor, in air (touching): 2 circuits 0.85, 3 circuits 0.79, 4 circuits 0.75, 6 circuits 0.72
- Grouping factor, buried (touching): 2 circuits 0.75, 3 circuits 0.65, 4 circuits 0.60, 6 circuits 0.50
- Conductor resistance at 20 deg C follows IEC 60228, corrected to the maximum operating temperature
- Allowable voltage drop: about 3 % for a branch circuit and about 5 % overall, depending on the code
How to use the calculator
- Select the calculation, the system (single-phase or three-phase) and the voltage.
- Enter the load, its unit and the power factor, plus the cable length and the allowable voltage drop.
- Select the material, the insulation, the installation method, the temperature and the grouping.
- Use parallel cables if the load is large and no single cable size is enough.
- Click Calculate, then Download PDF Result if you need a record.
Important notes
- Typical values only. The cable manufacturer data, the applicable code (IEC, NEC or IS) and your project specification are final.
- This calculator does not check short-circuit withstand, motor starting voltage drop, harmonics or protective device coordination.
- It covers low-voltage cables up to 1000 V. Medium and high voltage cables need different tables.
Worked example
Example 1 – 50 kW three-phase load, 100 m
415 V, power factor 0.85, copper XLPE cable on a tray in air, ambient 40 deg C, one circuit, voltage drop limit 3 %.
Current I = 50,000 / (1.732 x 415 x 0.85) = 81.8 A
Temperature factor = square root of (50 / 60) = 0.913, so the rating needed from the table = 81.8 / 0.913 = 89.6 A
Size by current: 16 mm² (table rating 100 A)
Voltage drop with 16 mm²: R = 1.15 x (1 + 0.00393 x 70) = 1.466 ohm/km, so drop = 1.732 x 81.8 x 0.1 x (1.466 x 0.85 + 0.08 x 0.527) = 18.3 V (4.4 %), which is more than 3 %
Voltage drop with 25 mm²: R = 0.927 ohm/km, drop = 11.77 V (2.84 %), which meets the limit
Selected size = 25 mm²
Example 2 – Single-phase 5 kW load, 30 m
230 V, power factor 0.90, copper PVC cable in air at 30 deg C, voltage drop limit 3 %.
Current I = 5000 / (230 x 0.90) = 24.2 A
Size by current: 4 mm² (rating 32 A)
Voltage drop with 4 mm² = 3.15 %, which is above 3 %
Voltage drop with 6 mm² = 4.86 V = 2.11 %
Selected size = 6 mm², chosen by voltage drop, not by current.
Example 3 – 400 A load with parallel cables
415 V three-phase, power factor 0.85, copper XLPE in air at 40 deg C, 500 ft (152.4 m), 2 parallel cables per phase, limit 3 %.
Current per cable = 400 / 2 = 200 A. Rating needed = 200 / 0.913 = 219.1 A, so size by current is 70 mm².
Size by voltage drop is 120 mm².
Selected size = 2 x 120 mm² per phase, derated capacity 631.7 A, voltage drop 10.98 V (2.65 %).
Example 4 – Current capacity of a 50 mm² cable
Copper XLPE, 50 mm², in air at 40 deg C, one circuit, 415 V three-phase, power factor 0.85.
Iz = 192 x 0.913 x 1 = 175.3 A
Maximum load = 1.732 x 415 x 175.3 / 1000 = 125.99 kVA = 107.09 kW
Common mistakes
- Choosing the cable only by current. For long runs, voltage drop often needs a bigger cable than current does.
- Ignoring the ambient temperature. A cable in a hot plant room or a rooftop tray carries much less current than its table rating.
- Forgetting the grouping factor when many cables share a tray or trench. Cables heat each other, so each one carries less.
- Using the power in kW as if it were kVA. The current depends on the power factor, so a low power factor needs a larger cable.
- Using the full length of a ring or the wrong length. Voltage drop depends on the one-way length from the source to the load.
- Choosing the same size for copper and aluminium. Aluminium has higher resistance and lower current capacity, so it needs a larger size.
- Ignoring motor starting current. A cable that works at full load may cause a large voltage dip during starting.
- Forgetting the short-circuit rating. The cable must withstand the fault current until the protective device trips.
- Using a single very large cable instead of parallel cables above about 300 mm². Parallel cables must have the same size, length and route to share current equally.
Frequently asked questions
How do I select a cable size?
Find the load current, apply the derating factors for temperature and grouping, pick the smallest cable whose rating is enough, then check the voltage drop for your length. The final size is the larger of the two.
What is the formula for cable current?
For a three-phase load, I = P / (square root of 3 x V x power factor). For a single-phase load, I = P / (V x power factor). P is in watts and V in volts.
What is the allowable voltage drop in a cable?
Many codes allow about 3 % for a branch circuit and about 5 % overall from the supply to the load. Some projects use a stricter limit, so check your specification.
How do I calculate voltage drop in a cable?
Voltage drop = factor x I x L x (R x cos phi + X x sin phi), where the factor is the square root of 3 for three-phase and 2 for single-phase, and L is the one-way length.
What is the temperature correction factor?
Cable ratings are given for a reference temperature, 30 deg C in air. When the surroundings are hotter, the cable can carry less current. The factor is the square root of ((max cable temperature – ambient) / (max cable temperature – 30)).
What is the grouping factor?
When cables run close together, they heat each other. The grouping factor reduces the current rating of each cable. For example, 3 circuits touching on a tray give a factor of about 0.79 in air.
What is the difference between PVC and XLPE cables?
PVC cable has a maximum conductor temperature of 70 deg C and XLPE of 90 deg C. The higher temperature lets an XLPE cable carry more current for the same size.
Copper or aluminium cable, which is better?
Copper has lower resistance and carries more current for the same size. Aluminium is lighter and cheaper, but needs a larger size, and careful termination. Aluminium is mostly used for larger sizes.
When should I use parallel cables?
Use parallel cables when the current is more than a single cable can carry, usually above 300 mm². All parallel cables must have the same size, length, material and route.
How do I find the maximum cable length?
Use the Maximum Cable Length mode. It divides the allowed voltage drop in volts by the voltage drop per metre at your load current.
Does this calculator check the short-circuit rating?
No. You must also check that the cable can withstand the fault current for the time the protective device takes to trip, and that the protection is coordinated with the cable.
Is this a replacement for a cable schedule?
No. It gives a quick preliminary size. The final cable schedule must use the manufacturer data, the applicable code and the project specification.
Related calculators: Voltage Drop Calculator, Amps to kW Calculator, Connected Load and Demand Load Calculator and kW to kVA Calculator.