TR to CFM and CFM to TR Calculator
Result
For guidance only. Airflow per TR depends on the climate, the coil selection, the supply air temperature and the latent load. Verify with the equipment datasheet, ASHRAE guidance and your project specification.
How the formula works
TR (tonne of refrigeration) is the unit of cooling capacity of an air conditioner. CFM (cubic feet per minute) is the volume of air that the indoor unit or air handler moves. The two are linked, because the air carries the heat away from the room. You can convert between them with a quick rule of thumb or with a more accurate formula based on the air temperature difference.
Method 1 – Rule of thumb
Airflow (CFM) = TR x CFM per TR
Capacity (TR) = airflow (CFM) / CFM per TR
A typical value is 400 CFM per TR. It is lower (about 350) for humid climates and higher (about 450) for dry climates.
Method 2 – Air temperature difference
Airflow (CFM) = TR x 12000 x SHR / (1.08 x delta T in deg F)
Capacity (TR) = 1.08 x CFM x delta T (deg F) / (12000 x SHR)
Where
- 1 TR = 12,000 BTU/h = 3.517 kW
- delta T = room air temperature minus supply air temperature. 1 deg C difference = 1.8 deg F difference.
- SHR = sensible heat ratio, the share of the cooling load that is sensible (temperature) heat and not latent (moisture) heat
- 1.08 = 60 x 0.075 lb/ft3 x 0.24 BTU/lb-F, the constant for standard air at sea level
- 1 CFM = 1.699 m3/h = 0.4719 L/s
Electrical performance (optional)
kW per TR = electrical input power (kW) / TR
COP = 3.517 x TR / electrical kW
EER = 12 x TR / electrical kW (BTU/h per watt)
Typical values used
- CFM per TR: about 350 for humid climates and split or window ACs, about 400 for standard comfort cooling, about 450 for dry climates
- Delta T (room minus supply air): about 8 to 14 deg C (14 to 25 deg F)
- Sensible heat ratio: about 0.70 for humid climates, 0.75 for typical comfort cooling, 0.90 for dry climates
How to use the calculator
- Select TR to CFM or CFM to TR, and then the method.
- For TR to CFM, select the cooling capacity. For CFM to TR, enter the airflow and its unit.
- For the rule of thumb, select the CFM per TR. For the temperature difference method, enter the delta T and select the sensible heat ratio.
- Optionally enter the electrical input power in kW to get kW/TR, COP and EER.
- Click Calculate, then Download PDF Result if you need a record.
Important notes
- Typical values only. The equipment datasheet, the coil selection and the project specification are final.
- The constant 1.08 is for standard air at sea level. At high altitude the air is thinner, so the real airflow needed is higher.
- The temperature difference method uses the sensible heat ratio, so the airflow it gives matches the sensible load. Latent load and coil selection can change the result.
Worked example
Example 1 – TR to CFM, rule of thumb
1.5 TR split AC, 400 CFM per TR.
Airflow = 1.5 x 400 = 600 CFM = 1019.4 m3/h = 283.2 L/s.
Cooling capacity = 1.5 x 3.517 = 5.28 kW = 18,000 BTU/h.
If the unit draws 1.6 kW: kW per TR = 1.6 / 1.5 = 1.067, COP = 3.517 / 1.067 = 3.30, EER = 12 / 1.067 = 11.25.
Example 2 – TR to CFM, temperature difference method
2 TR, delta T = 11 deg C (19.8 deg F), sensible heat ratio 0.75.
Airflow = 2 x 12000 x 0.75 / (1.08 x 19.8) = 18000 / 21.384 = 841.8 CFM.
This is 420.9 CFM per TR, which is close to the 400 rule of thumb.
Example 3 – CFM to TR, rule of thumb
An air handler moves 1200 CFM at 400 CFM per TR.
Capacity = 1200 / 400 = 3 TR = 10.55 kW = 36,000 BTU/h.
Example 4 – CFM to TR, temperature difference method
1200 CFM, delta T = 10 deg C (18 deg F), sensible heat ratio 0.75.
Capacity = 1.08 x 1200 x 18 / (12000 x 0.75) = 23328 / 9000 = 2.592 TR = 9.12 kW.
Common mistakes
- Using 400 CFM per TR for every project. The right value depends on the climate, the coil and the supply air temperature.
- Mixing delta T in deg C and deg F. The formula needs deg F, so a difference in deg C must be multiplied by 1.8.
- Using the room temperature as delta T. Delta T is room air minus supply air, not the difference to the outside air.
- Forgetting the sensible heat ratio. Without it, the formula only covers the sensible part of the load.
- Mixing airflow units. 1 CFM is 1.699 m3/h or 0.4719 L/s, so check the unit before entering the airflow.
- Confusing TR with kW. 1 TR is 3.517 kW of cooling, not electrical power.
- Using the rated TR of a split AC as the load. The cooling load of the room must be calculated first, and the AC chosen to match it.
- Ignoring altitude. At high altitude the constant 1.08 is lower, so the airflow needed is higher.
- Choosing a very low airflow per TR to save fan power. The air can then be too cold and cause condensation and poor mixing in the room.
Frequently asked questions
How many CFM per TR?
A typical rule of thumb is 400 CFM per TR for comfort cooling. It is about 350 CFM for humid climates and about 450 CFM for dry climates.
How do I convert TR to CFM?
Multiply the TR by the CFM per TR. For example, 1.5 TR x 400 = 600 CFM. For a more accurate result, use the air temperature difference method.
How do I convert CFM to TR?
Divide the CFM by the CFM per TR. For example, 1200 CFM / 400 = 3 TR.
What is 1 TR in kW and BTU/h?
1 TR = 3.517 kW = 12,000 BTU/h. This is the heat needed to melt one short ton of ice in 24 hours.
What is the formula for CFM from TR and delta T?
CFM = TR x 12000 x SHR / (1.08 x delta T in deg F). If you assume SHR = 1, this gives only the sensible airflow.
What is the sensible heat ratio?
It is the sensible cooling load divided by the total cooling load. A comfort cooling system often has an SHR of about 0.75, because part of the load is moisture removal.
What delta T should I use for air conditioning?
The difference between the room air and the supply air is usually about 8 to 14 deg C (14 to 25 deg F) for comfort cooling. A smaller delta T needs more airflow.
How do I convert CFM to m3/h and L/s?
1 CFM = 1.699 m3/h = 0.4719 L/s. The calculator shows all three units in the result.
What is the airflow of a 1.5 TR split AC?
About 600 CFM at 400 CFM per TR, which is about 1020 m3/h. Many split ACs run a little lower, near 350 CFM per TR, for better dehumidification.
What are COP and EER?
Both measure efficiency. COP = cooling kW / electrical kW. EER = cooling BTU/h / electrical watts. EER is about 3.41 times the COP.
Does altitude change the airflow?
Yes. Air is thinner at altitude, so the constant 1.08 is lower and more airflow is needed for the same cooling. Correct the value for high-altitude projects.
Is this calculator a replacement for a load calculation?
No. It converts between capacity and airflow only. The cooling load of the space must come from a proper heat load calculation, and the equipment from the manufacturer data.