Many cable sizing mistakes begin with one shortcut: picking a cable only because its current rating looks big enough. A cable that carries the current safely can still waste energy over a long route, or fail badly during a short circuit. This guide walks through the full selection process in a clear order, with one worked example you can repeat by hand.
What you need before you start
Collect these inputs first. Missing even one of them is the usual reason two engineers get different answers for the same load.
| Input | Why it matters |
|---|---|
| Load power (kW) or current (A) | Starting point for the design current. |
| Supply voltage and phases | Decides which current formula and which voltage drop figure to use. |
| Power factor | Converts kW into amps. A lower power factor means more current for the same kW. |
| Route length | Voltage drop grows directly with length. |
| Installation method | Cable in open air, in conduit, on a tray or buried loses heat differently. |
| Ambient temperature | A hotter surrounding reduces the safe current. |
| Number of cables grouped together | Neighbouring cables heat each other. |
| Conductor and insulation type | Copper or aluminium, PVC or XLPE: each has its own rating table. |
| Protective device rating and fault level | Needed for the overload and short-circuit checks. |
Step 1: Find the design current
The design current (Ib) is the current the circuit actually has to carry.
Three-phase: Ib = P ÷ (√3 × V × PF)
Here P is in watts, V is the supply voltage in volts (line-to-line for three-phase) and PF is the power factor. For a motor, use the electrical input power, which is the shaft power divided by efficiency. If you only have kW or kVA figures, the Amps to kW Calculator converts between them quickly.
Step 2: Choose the protective device rating
Select the breaker or fuse rating (In) so that it is not smaller than the design current. The three values must follow this order:
Iz is the current-carrying capacity of the cable after all derating factors are applied. If the breaker is bigger than what the cable can safely carry, the breaker will not protect the cable from overload.
Step 3: Apply the derating factors
Cable catalogues publish ratings under standard reference conditions. Real sites rarely match them, so the rating must be reduced with correction factors.
| Condition | Effect on the rating |
|---|---|
| Ambient temperature above the reference value | Rating goes down. |
| Several cables grouped closely | Rating goes down as the group grows. |
| Cable in conduit or surrounded by thermal insulation | Rating goes down because heat cannot escape easily. |
| Buried cable in dry or high-resistivity soil | Rating goes down. |
| Strong harmonic currents in the neutral | May require a larger neutral or a bigger cable. |
Multiply the applicable factors to get one combined derating factor (Cd). Then work backwards to the rating you need from the catalogue:
Step 4: Pick a size from the catalogue
Open the cable maker’s current rating table for your exact cable type: conductor material, insulation, number of cores and installation method. Choose the smallest size whose tabulated rating is equal to or greater than It. This is your size from the current check.
Step 5: Check the voltage drop
A cable that passes the current check can still be too thin for a long route. Cable catalogues list a voltage drop value in mV per ampere per metre (mV/A/m) for each size.
Vd (%) = Vd ÷ supply voltage × 100
L is the one-way route length in metres. Many designers keep the drop to about 3% on a branch or feeder and about 5% from the origin to the farthest point, but the correct limit depends on the code and on your project specification, so confirm it before you design.
Step 6: Check short-circuit withstand
During a fault, the conductor heats up very quickly. The cross-section must be large enough to survive until the protective device clears the fault.
S is the conductor area in mm², I is the fault current in amperes, t is the clearing time in seconds, and k is a constant that depends on the conductor and insulation. Commonly used values are about 115 for copper with PVC insulation and about 143 for copper with XLPE insulation. Confirm the value in the standard or the manufacturer’s data.
Step 7: Take the largest result
You now have three sizes: one from the current check, one from the voltage drop check and one from the short-circuit check. The final cable size is the largest of the three. Short routes are usually decided by the current check, while long routes are very often decided by voltage drop.
Worked example: 22 kW three-phase load
All cable ratings and mV/A/m figures below are illustrative numbers for learning. For a real job, replace them with values from your own cable catalogue.
| Given data | Value |
|---|---|
| Load | 22 kW, three-phase, 415 V, PF 0.85 |
| Cable | Copper, XLPE, 3-core and earth, clipped in a group |
| Route length | 60 m |
| Derating | Ambient factor 0.90 and grouping factor 0.89 |
| Fault level | 3 kA, cleared in 0.1 s |
Design current
Protective device and current check
The next standard breaker above 36 A is In = 40 A. The combined derating factor is 0.90 × 0.89 ≈ 0.80.
Suppose the catalogue lists 6 mm² at 46 A and 10 mm² at 63 A. The 6 mm² cable falls short of 50 A, so the current check gives 10 mm².
Voltage drop check
Suppose the catalogue gives 3.8 mV/A/m for 10 mm² (three-phase).
Vd (%) = 8.2 ÷ 415 × 100 ≈ 1.98%
This is well within a 3% limit, so 10 mm² passes.
Short-circuit check
10 mm² is larger than 6.6 mm², so it passes.
What happens if the route is longer?
Now keep everything the same but change the route length to 150 m. The current and short-circuit checks do not change, but the voltage drop does. Assumed mV/A/m figures: 10 mm² = 3.8, 16 mm² = 2.4, 25 mm² = 1.5.
| Size | Voltage drop at 150 m | Drop in % | Against a 3% limit |
|---|---|---|---|
| 10 mm² | 20.5 V | 4.94% | Fails |
| 16 mm² | 13.0 V | 3.12% | Fails narrowly |
| 25 mm² | 8.1 V | 1.95% | Passes |
The same load now needs 25 mm². The current rating of the cable did not change, but the length did. This is why you should never size a long cable on current alone.
Copper or aluminium?
Aluminium conducts roughly 60% as well as copper, so it needs about 1.6 times the cross-section for the same resistance. It is lighter and cheaper per metre, and it is mostly used for larger sizes and heavy feeders. Its terminations need more care, and many codes set a minimum size for aluminium conductors, so check the rule that applies to your project.
Common cable sizing mistakes
- Sizing on current alone and never checking voltage drop on long runs.
- Skipping derating for heat, grouping and installation method.
- Choosing a breaker larger than the cable can carry, which breaks the Ib ≤ In ≤ Iz rule.
- Using a single-phase formula for a three-phase load, or forgetting the power factor.
- Ignoring motor starting current and the voltage dip it causes.
- Mixing up catalogues, for example using a PVC rating for an XLPE cable.
- Forgetting the termination: a very large cable may not fit the breaker or lug.
Quick checklist before you finalise
- Design current calculated with the correct power factor and phases
- Breaker rating selected so that Ib ≤ In ≤ Iz
- Derating factors applied and a size picked from the right catalogue table
- Voltage drop checked over the real route length
- Short-circuit withstand checked with the actual fault level and trip time
- Final size is the largest of the three checks, and it fits the terminals
Frequently asked questions
Does cable size depend on length?
The current rating of a cable does not depend on its length, but the voltage drop does. A long route may need a bigger cable even when the current is small.
What does mV/A/m mean?
It is the voltage lost for every ampere flowing through every metre of cable. Multiply it by the current and the length, then divide by 1000, to get the drop in volts.
Which matters more, current rating or voltage drop?
Both must pass. Short runs are usually controlled by the current rating, and long runs are usually controlled by voltage drop.
Can I use a bigger cable than the calculation says?
Yes. A larger cable reduces losses and voltage drop and leaves room for future load. The cost goes up, and you must make sure it still fits the terminals and glands.
Is a cable size calculator enough for the final design?
A calculator is good for quick checks and early design. The final selection should be verified against the cable manufacturer’s data, the applicable code and a qualified engineer.
Try it yourself
Enter your own load, voltage and route length in the calculator and compare the result with the hand calculation above.
⚡ Open the Cable Size Calculator