A fire alarm system has to keep working exactly when the building’s mains power is most likely to fail. That is the job of the standby battery in the control panel. If the battery is too small, the system can go silent in the middle of an emergency, or it may fail its first power-cut test during commissioning. This guide explains how to calculate the battery capacity in ampere-hours (Ah), step by step, with one worked example and four different cases you can repeat by hand.
Standby load and alarm load
A fire alarm system sits in one of two states, and it draws very different current in each.
| State | What is happening | Current | Duration |
|---|---|---|---|
| Standby (quiescent) | Mains has failed. The panel, detectors and modules are only monitoring. Nothing is sounding. | Low | Long, many hours |
| Alarm | A fire has been detected. Sounders, strobes and relay outputs are active, and the panel’s indicators are lit. | High | Short, minutes |
The two states are sized separately and then added. Long standby time at a small current and short alarm time at a large current can end up with very different Ah, as the worked example below shows.
Step 1: List every device that draws from the battery
Go through the system drawing or the device schedule and list everything powered from the panel’s battery supply. A device left off the list is the most common reason a battery turns out too small.
- The control panel itself, including its display and network or communication cards
- Smoke, heat and multi-sensor detectors
- Manual call points
- Sounders, bells and strobes (in alarm, these are usually the largest load)
- Input and output modules, relay modules, and door-holder or damper control outputs
- Any auxiliary outputs, for example a 24 V supply to external equipment
Step 2: Find the standby and alarm current of each device
Read both values for every device from its manufacturer’s data sheet. The panel’s own standby and alarm currents are usually given in its installation manual, often for a stated battery voltage. Use the figures at the battery voltage the panel actually runs on, typically 24 V for panels of this kind.
Step 3: Add up the totals
Total alarm current = sum of (quantity × alarm current of each device)
Counting every detector at its full alarm current is a conservative method, because in a real fire only some devices go into alarm. Some specifications define a smaller number of devices in alarm. Follow the method your project specification asks for, and if it says nothing, the conservative method is the safer choice.
Step 4: Decide the standby and alarm durations
These come from the standard or the specification you are designing to, and from the local fire authority. They are not the designer’s free choice. The figures below are commonly seen values, given for orientation only.
| Duration | Commonly seen requirement |
|---|---|
| Standby time | 24 hours is common. Some specifications ask for a longer time, such as 72 hours, especially where no standby generator is present. |
| Alarm time | Often between 5 and 30 minutes after the standby period, depending on the standard. Voice evacuation systems usually need longer. |
Examples of standards that set such requirements include NFPA 72, the EN 54 series with BS 5839-1, and in India IS 2189 together with the National Building Code. Always confirm the exact values in the edition that applies to your project.
Step 5: Calculate the capacity
Alarm capacity (Ah) = total alarm current (A) × alarm time (h)
Alarm time in hours = minutes ÷ 60
Required capacity = standby capacity + alarm capacity
Step 6: Apply the derating factor
A battery loses capacity as it ages, and it also gives less capacity in cold conditions. A common rule is to treat a battery as worn out when it can deliver only about 80% of its rated capacity. To make sure the system still works at that point, divide by 0.8, which is the same as multiplying by 1.25.
Many designers use a factor between about 1.2 and 1.3. Use the value your specification calls for, and use a larger one if the battery will sit in a cold room.
Step 7: Choose a standard battery
Sealed lead-acid batteries come in a limited range of sizes, with 7, 12, 18 and 26 Ah being commonly available. Pick the next standard size at or above the design capacity. Panels at 24 V use two 12 V batteries connected in series. Connecting two batteries in series raises the voltage, but the capacity in Ah stays the same. Two 12 V 12 Ah batteries in series make a 24 V 12 Ah battery, not 24 Ah.
Worked example: a building with 60 detectors
All current values below are illustrative numbers for learning. For a real job, replace them with the figures from your own data sheets.
| Device | Qty | Standby each | Alarm each | Standby total | Alarm total |
|---|---|---|---|---|---|
| Control panel | 1 | 250 mA | 350 mA | 250 mA | 350 mA |
| Smoke detectors | 60 | 0.3 mA | 0.4 mA | 18 mA | 24 mA |
| Manual call points | 10 | 0.2 mA | 0.2 mA | 2 mA | 2 mA |
| Sounders | 12 | 0.5 mA | 25 mA | 6 mA | 300 mA |
| Total | 276 mA | 676 mA |
So the total standby current is 0.276 A and the total alarm current is 0.676 A. The design requirement in this example is 24 hours of standby followed by 30 minutes of alarm.
Alarm capacity = 0.676 × 0.5 = 0.338 Ah
Required capacity = 6.624 + 0.338 = 6.962 Ah
With the 1.25 factor = 6.962 × 1.25 ≈ 8.70 Ah
Look at where the capacity went: 6.624 of the 6.962 Ah, about 95%, is used during standby. The alarm period, which sounds like the dramatic part, uses only about 5%. This is the most useful thing to understand about battery sizing, and the next section shows it in numbers.
What if the requirement changes?
Keeping the same devices, here is how the answer moves when one thing changes.
| Case | Calculation | Design capacity | Standard size |
|---|---|---|---|
| Base: 24 h standby + 30 min alarm | (6.624 + 0.338) × 1.25 | 8.70 Ah | 12 Ah |
| Shorter alarm: 24 h + 5 min | (6.624 + 0.056) × 1.25 | 8.35 Ah | 12 Ah |
| Double the sounders (24 instead of 12) | (0.282 × 24 + 0.976 × 0.5) × 1.25 | 9.07 Ah | 12 Ah |
| Longer standby: 72 h + 30 min | (0.276 × 72 + 0.338) × 1.25 | 25.26 Ah | 26 Ah |
You can test your own numbers with the Fire Alarm Battery Calculator.
Check the charger too
The panel’s charger has to do two jobs: supply the panel’s own load and recharge the battery after a mains failure. Many specifications also set a recharge time, often within 24 to 48 hours, so check the one that applies to your project. Here is a rough check using the base example.
Plus the panel’s own standby load = 0.276 A
Rough minimum charger output = 0.5 + 0.276 ≈ 0.78 A
This is only a rough check, because charging is not perfectly efficient and a real charger needs some spare capacity. The panel manual also states the largest battery size its charger can handle. If the calculated battery is larger than that, you need a bigger charger or a separate power supply unit.
Common mistakes
- Forgetting the standby time. Looking only at the alarm current gives a battery far too small.
- Leaving out devices such as network cards, relay modules and auxiliary outputs.
- Skipping the ageing factor, so that the battery passes on day one and fails a year or two later.
- Adding two series batteries’ Ah together. Series connection adds voltage, not capacity.
- Using currents at the wrong voltage, for example 12 V figures for a 24 V panel.
- Using one set of hours for every project. The standby and alarm times come from the applicable standard and the specification.
- Ignoring the charger limit and the physical space in the panel cabinet.
Quick checklist
- Every battery-powered device listed, including modules and auxiliary outputs
- Standby and alarm current taken from data sheets, at the right voltage
- Standby and alarm times taken from the applicable standard or specification
- Capacity calculated for both states and added
- Ageing factor applied and the next standard size chosen
- Charger rating and cabinet space checked
Frequently asked questions
How long should a fire alarm battery last?
It depends on the standard and the specification. A common requirement is 24 hours of standby followed by an alarm period of a few minutes to half an hour. Some projects ask for 72 hours of standby. Confirm the value with your specification and the local fire authority.
Why multiply by 1.25?
A battery is usually considered worn out at about 80% of its rated capacity. Dividing the requirement by 0.8, which is the same as multiplying by 1.25, makes sure the system still meets its duty near the end of the battery’s life.
Do all detectors draw alarm current at once?
In a real fire, only some devices go into alarm. The conservative method counts all of them, and some specifications define a smaller number. If your specification says nothing, the conservative method is the safer choice.
Can I fit a larger battery than the calculation says?
Yes, as long as it fits in the cabinet and the panel’s charger is rated for it. A larger battery gives more margin, but it also takes longer to recharge.
What if the battery needed is bigger than the panel can charge?
Use a panel with a larger charger, or a separate power supply with its own battery for part of the load, such as a group of sounders. Follow the panel manufacturer’s instructions for this.
Is a calculator enough for the final design?
A calculator is good for a first estimate and for checking the arithmetic. The final design must use the manufacturer’s data, the applicable standard and the approval of a qualified engineer and the local fire authority.
Try it yourself
Enter your own device quantities and currents in the calculator and compare the result with the hand calculation above.
🔋 Open the Fire Alarm Battery Calculator