Imported machines, solar kits, EV chargers and welding equipment often arrive with cables marked in AWG, while Indian drawings, cable catalogues and wiring rules use square millimetres (mm²). The two systems do not line up neatly, and a careless guess can leave you with a cable that is too thin for the load. This guide explains how AWG works, shows the formula and a conversion chart, and works through four examples so that you can convert between the two systems with confidence.
How AWG works
AWG comes from the number of drawing steps a wire goes through when it is pulled to a smaller size. More steps mean a thinner wire, so the number goes up as the wire gets thinner. That is why 10 AWG is thicker than 14 AWG. For very thick conductors the numbering continues as 1/0, 2/0, 3/0 and 4/0 (said as “one-aught”, “two-aught” and so on), where a bigger number before the slash again means a thicker wire.
Metric sizing is simpler. A 2.5 mm² cable has a conductor with a cross-section of 2.5 square millimetres. Standard metric sizes follow the IEC 60228 series, such as 0.5, 0.75, 1, 1.5, 2.5, 4, 6, 10, 16, 25, 35, 50, 70, 95, 120, 150, 185, 240 and 300 mm².
The AWG formula
AWG sizes follow an exact mathematical rule, so you can calculate any size yourself. Let n be the AWG number, treating 1/0 as 0, 2/0 as −1, 3/0 as −2 and 4/0 as −3.
Area (mm²) = π × diameter² ÷ 4
To go the other way, from a diameter back to the AWG number:
A quick mental rule
The formula leads to three easy rules you can use without a calculator:
- Every 3 AWG steps down (for example 12 to 9), the area doubles.
- Every 6 AWG steps down, the diameter doubles.
- Every 10 AWG steps down, the area becomes about 10 times larger.
As a check, 10 AWG is about 5.26 mm². Three steps thinner is 13 AWG at about 2.63 mm², and six steps thinner is 16 AWG at about 1.31 mm², which matches the chart below.
AWG to mm² conversion chart
The table gives the solid-copper area of each AWG size, the resistance of copper at 20 °C, and the next standard metric size at or above the area. Values are rounded, so another published chart may differ in the last digit.
| AWG | Diameter (mm) | Area (mm²) | Resistance (Ω/km) | Next standard metric size at or above |
|---|---|---|---|---|
| 18 | 1.02 | 0.82 | 20.9 | 1 mm² |
| 16 | 1.29 | 1.31 | 13.2 | 1.5 mm² |
| 14 | 1.63 | 2.08 | 8.29 | 2.5 mm² |
| 12 | 2.05 | 3.31 | 5.21 | 4 mm² |
| 10 | 2.59 | 5.26 | 3.28 | 6 mm² |
| 8 | 3.26 | 8.37 | 2.06 | 10 mm² |
| 6 | 4.11 | 13.3 | 1.30 | 16 mm² |
| 4 | 5.19 | 21.2 | 0.815 | 25 mm² |
| 2 | 6.54 | 33.6 | 0.513 | 35 mm² |
| 1/0 | 8.25 | 53.5 | 0.322 | 70 mm² |
| 2/0 | 9.27 | 67.4 | 0.256 | 70 mm² |
| 3/0 | 10.4 | 85.0 | 0.203 | 95 mm² |
| 4/0 | 11.7 | 107 | 0.161 | 120 mm² |
Rounding up is the cautious choice, because it keeps the conductor at least as large as the original. For 1/0 AWG, the 50 mm² size is about 6% smaller, so the next size up is 70 mm². Whether a slightly smaller size is acceptable depends on the load, the cable length and the code, so check before you use it.
Worked example 1: 12 AWG to mm²
Convert a 12 AWG conductor to a metric size.
Area = π × 2.05² ÷ 4 ≈ 3.31 mm²
Worked example 2: 6 mm² to AWG
Now convert the other way. A 6 mm² conductor has this diameter:
n = 36 − 39 × ln(2.76 ÷ 0.127) ÷ ln(92)
n = 36 − 39 × 3.08 ÷ 4.52 ≈ 36 − 26.6 ≈ 9.4
So 6 mm² sits between 10 AWG (5.26 mm²) and 9 AWG (6.63 mm²), but 9 AWG is an uncommon size in practice.
Worked example 3: a 14 AWG power cord
An imported machine comes with a 14 AWG supply cord, and you need to replace it with a metric cable locally.
| Metric size | Compared with 2.08 mm² |
|---|---|
| 1.5 mm² | About 28% less copper. Too thin. |
| 2.5 mm² | About 20% more copper. The right replacement. |
| 4 mm² | About 92% more copper. Larger than needed, but still safe. |
Worked example 4: what happens if you round down
A 10 A single-phase load on a 230 V supply is fed through a cable that is 30 m long, so the current travels 60 m in total (out and back). The existing cable is 12 AWG, and someone suggests using 2.5 mm² because it “looks close”. Here is the voltage drop for each choice, using the resistance of copper at 20 °C.
| Cable | Resistance (Ω/km) | Resistance over 60 m | Voltage drop at 10 A | Drop as % of 230 V |
|---|---|---|---|---|
| 12 AWG (3.31 mm²) | 5.21 | 0.313 Ω | 3.13 V | 1.36% |
| 2.5 mm² | 6.90 | 0.414 Ω | 4.14 V | 1.80% |
| 4 mm² | 4.31 | 0.259 Ω | 2.59 V | 1.12% |
Large cables: kcmil and MCM
North American catalogues give very large conductors in kcmil (also written MCM) instead of AWG. One kcmil is 1,000 circular mils, which equals about 0.5067 mm². For example, a 250 kcmil conductor has an area of about 250 × 0.5067 ≈ 127 mm², so the next standard metric size at or above it is 150 mm².
Stranded and solid wire
The AWG number is defined for a solid conductor. A stranded wire marked with the same AWG is made so that its total copper area matches that of the solid wire, so the electrical size is the same. Its overall diameter is slightly bigger, because small gaps remain between the strands. Always compare the copper area, not the outside diameter.
Why the area matters more than the name
A conductor’s resistance is inversely proportional to its area. For copper at 20 °C, a handy approximation is:
Less area means more resistance, more voltage drop and more heat. That is why the conversion must keep the copper area at least equal, and why the full cable selection should also check current and voltage drop, as described in our cable size selection guide.
Do not carry current ratings across systems
An AWG size and a metric size that are close in area do not always have the same safe current in a given code. Current ratings depend on the insulation, the ambient temperature, how the cable is installed and the standard being followed (for example NEC for AWG sizes and IS or IEC for metric sizes). Convert the size first, then read the current rating from the table for the standard that applies to your installation.
Common mistakes
- Thinking a bigger AWG number is a thicker wire. It is the opposite.
- Comparing the numbers across systems, for example treating 14 AWG as if it were 1.5 mm². It is about 2.08 mm².
- Rounding down to the nearest metric size and ending up with a thinner conductor.
- Comparing outside diameter of stranded wire instead of the copper area.
- Copying the current rating from one standard to the other without checking the installation conditions.
- Forgetting voltage drop on long runs, even when the current is well within the limit.
- Mixing copper and aluminium. An aluminium conductor needs a larger area than copper for the same resistance.
Quick checklist
- Find the copper area of the AWG size from the chart or the formula
- Choose the next standard metric size at or above that area
- Check the current rating in the standard that applies to your installation
- Check the voltage drop over the real cable length
- Check that the conductor fits the terminals and the glands
Frequently asked questions
Is 10 AWG the same as 6 mm²?
No. 10 AWG is about 5.26 mm², which is smaller than 6 mm². The 6 mm² size lies between 10 AWG and 9 AWG.
Which is thicker, 10 AWG or 12 AWG?
10 AWG is thicker. A smaller AWG number means a thicker conductor.
What does 1/0 or 2/0 AWG mean?
These are sizes thicker than 1 AWG. They are said “one-aught” and “two-aught”, and a bigger number before the slash means a thicker conductor. 1/0 is about 53.5 mm² and 2/0 is about 67.4 mm².
How do I convert AWG to mm² quickly?
Use the chart above, or use the quick rule that every 3 AWG steps change the area by a factor of 2. Starting from 10 AWG at about 5.26 mm², a size 3 steps thicker (7 AWG) is about 10.5 mm².
Can I use a metric cable instead of an AWG cable?
Yes, if the metric cable has at least the same copper area and its current rating and voltage drop are acceptable for the installation under the standard you follow.
Is a converter enough for a final design?
A converter is good for quick checks. The final cable selection should be verified against the applicable code, the cable manufacturer’s data and a qualified engineer.