Electrical Calculators

Free electrical calculators for load, current, cable size and voltage drop. Each tool explains its formula, shows a worked example and gives you a PDF result.

9Live calculators
100%Free, no signup
PDFOne-click download

All Electrical Calculators

Standard-based tools with a PDF result. Free to use, no signup.

9
Electrical

⚡ Amps to kW calculator

Convert amps to kW or kW to amps for single phase, three phase and DC supplies, with kVA, kVAr, HP and a downloadable PDF result.

Open calculator
Electrical

🔌 Appliance Power Consumption Calculator

Calculate the energy used by any appliance in kWh (units) per day, month and year, with running cost, usage time and average power.

Open calculator
Electrical

🧵 Cable Size Calculator

Select the cable size for a load using current capacity, derating factors and voltage drop, for copper and aluminium cables.

Open calculator
Electrical

🧲 Capacitor Bank Calculator

Select an APFC capacitor bank by kW, power factor, voltage and detuned reactor, with step size, number of steps and a downloadable PDF result.

Open calculator
Electrical

📊 Connected Load and Demand Load Calculator

Calculate connected load, maximum demand, kVA and current using demand and diversity factors, with a standard transformer size and a PDF result.

Open calculator
Electrical

🧾 Electricity Bill Calculator

Calculate your electricity bill from units consumed using flat or slab tariffs, with fixed charge, surcharge and tax, or find units from a bill.

Open calculator
Electrical

⚡ kW to kVA and kVA to kW Calculator

Convert kW to kVA or kVA to kW using the power factor, and get kVAR, power factor angle and current for single or three phase supply.

Open calculator
Electrical

⚡ VA to Watts Calculator

Convert VA to watts or watts to VA using the power factor, and get the current for single or three phase supply.

Open calculator
Electrical

📉 Voltage Drop Calculator

Calculate voltage drop in volts and percent for single phase, three phase and DC cables, with cable power loss and the minimum cable size for your limit.

Open calculator
No match. Try a different word.

About Electrical Calculators

Every electrical design, from a single room to a whole building, rests on four questions: how much power is needed, how much current that power draws, which cable can carry that current safely, and how much voltage is lost on the way. The electrical calculators on this page are arranged around those questions, so you can move from a list of loads to a checked circuit without jumping between spreadsheets.

The tools cover conversions between watts, kW, VA, kVA and amps, connected and demand load, cable and capacitor sizing, and the running cost of equipment. Each one shows its formula, so you can see which assumptions, such as supply voltage or power factor, drive the answer.

Electrical results are only as good as their inputs. Use the rated voltage of your supply, the real power factor of your equipment where it is known, and the actual route length of the cable, then compare the output with the requirements of the electrical code that applies to your project.

Every calculator explains the formula behind the result and lists common mistakes, so you can verify the answer instead of trusting a black box. Results are for estimation and learning, so always confirm final designs against the applicable code and with a qualified engineer.

How Electrical calculations fit together

The result of one step usually becomes the input of the next. This is a practical order to follow when you check a design.

  1. List every load. Write down each item with its rating, supply voltage and whether it is single-phase or three-phase.
  2. Convert power to current. Single phase uses I = P ÷ (V × PF). Three phase uses I = P ÷ (√3 × V × PF). Choosing the wrong one is the most common source of error.
  3. Apply the demand factor. Add up the connected loads, then reduce them to the demand load that is realistic when not everything runs together.
  4. Choose the cable. Pick a size that carries the current after derating for temperature and grouping, then check the voltage drop over the real route length.
  5. Look at the power factor. A low power factor raises current and can attract penalties on some tariffs. A capacitor bank is the usual correction.
  6. Estimate the running cost. Multiply kW by the hours of use and by the tariff to see what the equipment costs over a month.

Worked Electrical examples you can verify by hand

These short examples show the arithmetic behind the tools. The numbers are illustrative, so replace them with your own project values.

Current of a three-phase load

A load takes 15 kW from a 415 V three-phase supply at a power factor of 0.85.

I = P ÷ (√3 × V × PF)I = 15,000 ÷ (1.732 × 415 × 0.85)

≈ 24.6 A line current, before any allowance for motor starting current

Demand load of a small building

The connected load is 80 kW and the expected demand factor is 0.7. Demand factors come from the code, the client brief or past project data.

Demand load = connected load × demand factor= 80 × 0.7

56 kW to be used when sizing the supply

Capacitor bank for power factor correction

A 100 kW load runs at a power factor of 0.80 and the target is 0.95.

kVAr = kW × (tan φ1 − tan φ2)= 100 × (0.750 − 0.329)

≈ 42 kVAr of capacitor bank

Monthly running cost of an appliance

A 1.5 kW appliance runs 8 hours a day for 30 days at a tariff of ₹8 per unit.

Energy = 1.5 × 8 × 30 = 360 kWhCost = 360 × 8

₹2,880 per month

Common mistakes to avoid

Most calculation errors come from small habits, not from hard formulas.

  • Treating kW and kVA as the same.Nameplates often give kVA while loads are quoted in kW. The power factor links them.
  • Using the wrong phase formula.Applying the single-phase formula to a three-phase load overstates the current by about 73%, and the reverse mistake understates it, which can leave a cable or breaker undersized.
  • Ignoring cable derating.High ambient temperature, grouped cables and the way a cable is installed all reduce the current it can carry.
  • Checking current but not voltage drop.A cable can be thermally safe and still too thin for a long run.
  • Forgetting motor starting current.Starting current is several times the running current and affects the choice of protective device.
  • Using one tariff rate for everything.Many tariffs have slabs, demand charges or time-of-day rates, so a single rate gives only a rough cost.

Electrical terms in plain words

Short definitions of the terms you will meet in these calculators.

kW
Real power, the part that does useful work such as turning a motor or producing heat and light.
kVA
Apparent power, the total the supply must deliver. It equals kW divided by the power factor.
Power factor
The ratio of kW to kVA. A value close to 1 means the supply is used efficiently.
Connected load
The sum of the ratings of all installed equipment on a circuit or building.
Demand load
The part of the connected load expected to run at the same time.
Voltage drop
The voltage lost along a cable because of its resistance. It grows with current and length.
kVAr
Reactive power, supplied by a capacitor bank to improve the power factor.
Earthing
A low-resistance path that lets fault current flow to the ground so protective devices can operate.

Frequently asked questions

Quick answers about the Electrical calculators.

Are the Electrical calculators free?

Yes. All calculators on this page are free to use and do not need a signup or login.

Do the calculators show the formula?

Yes. Each calculator explains the formula behind the result, with a worked example and a list of common mistakes.

Which formula should I use for a three-phase load?

Use I = P ÷ (√3 × V × PF), where V is the line-to-line voltage. For a single-phase load use I = P ÷ (V × PF).

Why does power factor matter?

For the same kW, a lower power factor means more current. That needs larger cables and equipment and can lead to penalties on some electricity tariffs.

How do I choose a cable size?

Start from the load current, apply derating factors for temperature, grouping and installation method, then check the voltage drop over the actual length. Always confirm against the applicable code.

What is the difference between VA and watts?

VA is apparent power and watts are real power. They are equal only when the power factor is 1, as with a purely resistive load.

Does a capacitor bank reduce my energy bill?

It reduces reactive power and the current drawn from the supply. The saving depends on your tariff, because it does not reduce the kWh used by the equipment itself.

How accurate is a running cost estimate?

It is as accurate as the hours of use, the real load and the tariff you enter. Treat it as a planning figure and compare it with your actual bill.

Can I use the results for final design?

The results are for estimation and learning. Please verify them against the applicable code and with a qualified engineer before final design or construction.

Looking for another calculator?

Browse every MEP calculator in one place, enter your values and get a clear, explained result.

⚡ View all calculators