Choosing an air conditioner by room area alone is the most common way to end up with the wrong size. A unit that is too small runs all day and never reaches the set temperature. A unit that is too large costs more, and a fixed-speed one can switch on and off so often that the room stays cool but sticky. This guide explains how AC tonnage works, how to estimate the cooling load of a room step by step, and how to turn the answer into a standard size, with two worked examples you can repeat by hand.
What “ton” really means
The word comes from the old days of ice cooling. One ton of refrigeration is the cooling effect of melting one ton of ice over 24 hours. You do not need the history, only the three numbers below.
| Unit | Meaning | Relationship |
|---|---|---|
| TR (ton of refrigeration) | Cooling capacity, the size people quote for ACs | 1 TR = 12,000 BTU/h |
| BTU/h | Heat removed per hour | 1 kW = about 3,412 BTU/h |
| kW (cooling) | The same capacity in metric units | 1 TR ≈ 3.517 kW |
What decides the tonnage you need
Every item in the table adds heat that the AC must remove. Rooms with more of these items need a bigger unit even when the floor area is the same.
| Factor | Why it matters |
|---|---|
| Floor area and ceiling height | A bigger air volume holds more heat. |
| Floor level and roof exposure | A top-floor room under a sun-heated roof gains much more heat than a middle-floor room. |
| Sun-facing walls and windows | West and south-west exposure in the afternoon adds a large load, mostly through glass. |
| Number of people | Each person adds body heat and moisture. |
| Lights and equipment | Nearly every watt used by a computer, TV or lamp ends up as heat in the room. |
| Fresh air and door openings | Outside air brings both heat and humidity into the room. |
| Local climate | Hot and humid regions need more capacity than mild ones. |
A simple four-step estimate
A full cooling load calculation, such as the methods in ASHRAE or ISHRAE handbooks, is used for large buildings. For a single room, the simple method below is good enough for a first estimate. The factors in it are rule-of-thumb values for learning, so adjust them for your own climate.
Step 1: Base load from the floor area
The value of 70 BTU/h per square foot is a commonly used planning figure for an ordinary room with a standard ceiling height of about 10 ft in a hot climate. Use a lower figure for a well-shaded room and a higher one for a very hot, sunny location.
Step 2: Add the extra people
The base figure already assumes two people. For each additional person, add about 450 BTU/h, which is a typical value for a seated adult.
Step 3: Add the equipment heat
Add up the power of lights, computers, TVs and similar equipment that run at the same time. A 250 W desktop computer, for example, adds 250 × 3.41 ≈ 853 BTU/h.
Step 4: Correct for sun and floor level
Multiply the total by a correction factor. A shaded middle-floor room needs no correction. A top-floor room or a room with strong afternoon sun on a wall or window often needs an extra 10% to 20%. Then convert to tons:
Finally, choose the nearest standard size at or above the result. Common sizes are 1, 1.5 and 2 TR for room units.
A rough starting table
If you only want a first idea before doing the estimate, this table is a rough starting point for an ordinary room, about a 10 ft ceiling, moderate sun and two people. It is not a substitute for the four steps above.
| Room area | Starting size |
|---|---|
| Up to about 120 sq ft | 1 TR |
| About 120 to 170 sq ft | 1 TR if shaded, 1.5 TR if top floor or sunny |
| About 170 to 240 sq ft | 1.5 TR |
| Above about 240 sq ft | Do the full estimate, or consider two units |
Worked example 1: a bedroom
A bedroom measures 14 ft × 12 ft with a 10 ft ceiling. Two people sleep in it, and a 250 W desktop computer runs during the day. It is on the top floor, so the roof gets strong afternoon sun.
Base load = 168 × 70 = 11,760 BTU/h
Extra people = 0 (the base figure already covers two)
Computer = 250 × 3.41 ≈ 853 BTU/h
Subtotal = 11,760 + 853 = 12,613 BTU/h
Top-floor correction = 12,613 × 1.15 ≈ 14,505 BTU/h
Required tons = 14,505 ÷ 12,000 ≈ 1.21 TR
You can check your own numbers with the AC Tonnage Calculator, and the BTU Calculator converts the BTU figure into kW or tons.
Worked example 2: a living room, with and without strong sun
A living room measures 20 ft × 14 ft with a 10 ft ceiling. Four people sit in it in the evening, and a TV plus lights add up to 300 W. First, assume it is a shaded middle-floor room.
Base load = 280 × 70 = 19,600 BTU/h
Extra people = 2 × 450 = 900 BTU/h
TV and lights = 300 × 3.41 ≈ 1,023 BTU/h
Total = 19,600 + 900 + 1,023 = 21,523 BTU/h
Required tons = 21,523 ÷ 12,000 ≈ 1.79 TR
A 2 TR unit (24,000 BTU/h) fits this case comfortably. Now move the same room to the top floor with strong afternoon sun on a west wall:
Required tons = 24,751 ÷ 12,000 ≈ 2.06 TR
What does it cost to run?
Running cost depends on the electrical power the AC draws, not on its cooling capacity. A modern inverter AC draws different power at different times, because its compressor slows down once the room is cool. Here is a simple illustration with assumed numbers.
Running time = 8 hours per day
Tariff = ₹8 per unit (kWh)
Daily energy = 1.0 × 8 = 8 kWh
Daily cost = 8 × 8 = ₹64
Monthly cost = 64 × 30 = ₹1,920
These are illustrative values. The real figure depends on the AC’s efficiency rating, the temperature you set, how hot the day is and your electricity tariff, so use your own numbers in the AC Running Cost Calculator.
Too small or too big: what goes wrong
| If the AC is too small | If the AC is too large |
|---|---|
| It runs non-stop and still may not reach the set temperature. | A fixed-speed unit cools quickly and switches off, then restarts often. |
| Higher electricity use for poor comfort. | The room may feel cold but humid, because humidity needs running time to be removed. |
| The compressor works hard for long periods. | Higher purchase cost and more wear from frequent starts. |
An inverter AC copes with a slightly oversized capacity better than a fixed-speed one, because it can slow down instead of switching off. Even so, picking the right size first is the better approach.
Common mistakes
- Choosing by area alone and ignoring sun, floor level, people and equipment.
- Counting only the electrical power when comparing models. Capacity (TR or BTU/h) and efficiency are different things.
- Mixing cooling kW with electrical kW when estimating cost or when sizing the supply cable.
- Forgetting heat from equipment such as computers, kitchen appliances and servers.
- Ignoring fresh air in offices, shops and halls where doors open often.
- Sizing the unit but not the supply. The AC’s electrical load also needs a correctly sized cable and breaker.
Quick checklist
- Measure the room area and note the ceiling height
- Note the floor level and which walls and windows face the sun
- Count people and add up the watts of lights and equipment
- Convert the total load to BTU/h, then divide by 12,000
- Choose the nearest standard size at or above the result
- Check the electrical supply for the chosen unit
Frequently asked questions
How many square feet does a 1.5 ton AC cover?
About 150 to 250 sq ft, depending on sun and floor level
Is a bigger AC always better?
No. A unit that is much larger than the load costs more and, if it is a fixed-speed type, switches on and off often, which can leave the room humid. Choose the nearest standard size to the calculated load.
What is the difference between tons and BTU?
A ton is simply 12,000 BTU/h. So 1.5 tons equals 18,000 BTU/h, and 2 tons equals 24,000 BTU/h.
Does an inverter AC need a different tonnage?
The cooling load of the room is the same, so the tonnage calculation is the same. The difference is that an inverter AC adjusts its output and usually uses less electricity over a day than a fixed-speed AC of the same capacity.
How do I know the AC’s real electricity use?
Check the energy label and the data sheet for the rated input power and the efficiency rating. Actual use varies with the room temperature, the set point and the outside weather.
Is a calculator enough for a large hall or office?
For large rooms and commercial spaces, a detailed cooling load calculation by a qualified HVAC engineer is the right approach. A calculator gives a good first estimate, but it cannot replace a proper design.
Try it yourself
Enter your own room details in the calculator and compare the result with the hand calculations above.