Daily Water Demand and Tank Size: How to Calculate for a Building

Every water system in a building starts with one question: how much water will people use in a day? The pump, the pipes, the tanks and even the sewage treatment plant are all sized from that single number. If it is too low, the taps run dry in the evening peak. If it is too high, you pay for oversized tanks and pumps that you never needed. This guide shows how to estimate the daily demand step by step, how to turn it into underground and overhead tank sizes, and how to link it to the pump flow, with two worked examples you can repeat by hand.

The short answer: daily demand = number of people × water use per person per day, plus any extra uses. Storage is then a share of that daily demand. Many designers provide an underground tank of about one day’s demand and an overhead tank of roughly one third to one half of it, and then add a separate reserve for firefighting. The exact rule depends on how reliable the water supply is and on the code or authority that applies to your project.

What “lpcd” means

Water use is quoted in litres per capita per day (lpcd), which means litres used by one person in one day. Multiply it by the number of people and you have the daily demand in litres. Divide by 1,000 to get cubic metres, which is the unit tanks are usually designed in.

Unit Relationship
1 m³ 1,000 litres
1 m³ 35.31 cubic feet
1 ft³ 28.32 litres
1 US gallon 3.785 litres

For other conversions, the MEP Unit Converter changes volume and flow units together.

Step 1: Count the people

Use the real occupancy where you know it, and a design assumption where you do not. For a residential building, the common method is the number of flats multiplied by the number of persons per flat. For an office, use the number of staff plus an allowance for visitors. Always count the population the building will have at full occupancy, not only today’s occupancy.

Step 2: Choose the water use per person

The figure depends on the type of building, the climate and local habits, and it comes from the code or the authority’s guidelines. The values below are commonly quoted in Indian practice, for example from the National Building Code. Use them for orientation only and confirm the edition and the figure that apply to your project.

Type of building Commonly quoted figure
Residence (dwelling houses) about 135 lpcd
Hostel about 135 lpcd
Office about 45 lpcd
School (day school) about 45 lpcd
Hospital, hotel, restaurant, cinema and similar varies widely and often uses a per bed, per room or per seat basis, so take it from the code

These figures are normally meant to cover domestic use including flushing. Some projects split the demand into drinking and domestic water and flushing water. If yours does, follow the split in the specification.

Step 3: Calculate the daily demand

Daily demand (L/day) = people × lpcd
Daily demand (m³/day) = daily demand (L/day) ÷ 1000

Then add the extra uses that are not tied to people, such as landscaping, swimming-pool top-up, cooling tower make-up and a general allowance for visitors, domestic help and losses. If you want a quick check of the arithmetic, the Daily Water Demand Calculator does it for you.

Step 4: Decide the storage

Most buildings use two stores. An underground tank (UGT or sump) receives water from the municipal line or a borewell, and acts as a buffer for a day when the supply is short. An overhead tank (OHT) sits on the roof, and feeds the taps by gravity. A pump moves water between the two.

Tank Purpose Commonly used size
Underground tank (sump) Buffer against interruptions in the supply About one day’s demand, and more where the supply is unreliable
Overhead tank Gravity supply during peak hours and while the pump is off Roughly one third to one half of the daily demand
Fire water reserve Firefighting only Set by the fire code. Keep it separate from the domestic tanks

These proportions are common practice, not a universal rule. Supply reliability, building height, local by-laws and the owner’s requirement can all change them.

Step 5: Turn the volume into tank dimensions

Tank volume (m³) = length × width × water depth (all in metres)
Required plan area = volume ÷ water depth

Add a freeboard of roughly 0.3 m above the water level, so the tank does not overflow in normal use. The tank’s inside height is the water depth plus the freeboard.

Step 6: Find the pump flow

The pump has to move the daily demand into the overhead tank within the hours you allow it to run.

Pump flow (m³/h) = daily demand (m³) ÷ pumping hours per day

This flow is the starting point for the head and power calculation covered in our pump head and pump power guide.

Worked example 1: a residential block

A building has 50 flats with 4 people in each flat. The design uses 135 lpcd, a 10% allowance for visitors and domestic help, and an underground tank that holds one day’s demand. All values are illustrative numbers for learning.

People = 50 × 4 = 200
Domestic demand = 200 × 135 = 27,000 L = 27 m³/day
Allowance = 27,000 × 0.10 = 2,700 L
Total daily demand = 27,000 + 2,700 = 29,700 L = 29.7 m³/day

Tank sizes

Underground tank = 1 day × 29.7 = 29.7 m³, say 30 m³
Overhead tank = 29.7 ÷ 3 = 9.9 m³, say 10 m³ (10,000 L)
Tank Volume Water depth Plan area Example size
Underground 30 m³ 2.0 m 15 m² 5 m × 3 m, with 0.3 m freeboard
Overhead 10 m³ 2.0 m 5 m² 2.5 m × 2 m, with 0.3 m freeboard

Pump flow

Pumping time = 2.5 hours per day
Pump flow = 29.7 ÷ 2.5 = 11.88 m³/h, say 12 m³/h

Sewage for the treatment plant

A commonly used assumption is that about 80% of the water supplied ends up as sewage, but confirm the figure in your code or local rule.

Sewage = 29.7 × 0.80 = 23.76 m³/day, so a plant of roughly 25 m³/day capacity class
Result: the building needs about 29.7 m³ of water per day, a 30 m³ underground tank, a 10 m³ overhead tank and a transfer pump of about 12 m³/h. The sewage plant would be around 25 m³/day. You can compare the sewage figure with the STP Size Calculator.

Worked example 2: a small office

An office has 150 staff. It uses 45 lpcd, a 10% allowance for visitors, and an underground tank of one day’s demand.

Demand = 150 × 45 = 6,750 L
Allowance = 6,750 × 0.10 = 675 L
Total daily demand = 7,425 L = 7.425 m³/day
Underground tank = 7.425 m³, say 7.5 m³
Overhead tank = 7.425 ÷ 3 = 2.475 m³, say 2.5 m³
Result: the office needs about 7.4 m³ of water per day, a 7.5 m³ underground tank and a 2.5 m³ overhead tank. For the underground tank, a water depth of 1.5 m gives a plan area of 5 m², for example 2.5 m × 2 m.

How supply reliability changes the underground tank

The size of the underground tank depends strongly on how often the supply fails. Here is the residential block from example 1 with different storage periods:

Storage period Underground tank volume When it fits
Half a day 14.85 m³ A very reliable round-the-clock supply
One day 29.7 m³ A normal, mostly reliable supply
One and a half days 44.55 m³ A supply that sometimes fails for a day
Two days 59.4 m³ A supply available only a few hours on some days
What this shows: the same building can need a tank anywhere from about 15 m³ to about 59 m³, a fourfold difference, depending only on how dependable the supply is. Ask the owner or the local water authority about the real supply pattern before you fix the tank size.

Peak demand versus daily demand

The daily demand tells you about the tanks and the pump running hours, but water is not used evenly through the day. Use rises sharply in the morning and evening. Pipes, risers and booster pumps are therefore sized for the peak flow, which is several times the average hourly flow, and not for the daily average. The Pipe Sizing Calculator works from the flow you give it, so make sure you give it the peak value.

Common mistakes

  • Using the present occupancy instead of the full occupancy the building will have.
  • Using one lpcd figure for every building type. Offices, hospitals and hotels need their own values.
  • Forgetting the extra uses such as landscaping, pool top-up and cooling tower make-up.
  • Mixing fire water with domestic water in one tank volume. The fire reserve is a separate requirement.
  • Ignoring supply reliability when choosing the underground tank.
  • Mixing litres and cubic metres in the same calculation.
  • Sizing pipes on the daily average instead of the peak flow.
  • Leaving out freeboard and cleaning access when fixing the tank dimensions.

Quick checklist

  • Full-occupancy population decided
  • lpcd taken from the code for the building type
  • Extra uses and allowances added
  • Underground and overhead storage chosen for the supply pattern
  • Fire reserve kept separate
  • Pump flow worked out from the pumping hours
  • Tank dimensions checked with freeboard and access

Frequently asked questions

How much water does one person use per day?

For residences, a figure of about 135 litres per person per day is commonly used in Indian practice, but the real use depends on the climate, habits and fittings. Check the code or the authority’s guideline that applies to your project.

What size overhead tank do I need for a house?

Take the number of people multiplied by the litres per person per day, and then use roughly one third to one half of that figure as the overhead tank. For 5 people at 135 lpcd, the daily demand is 675 L, so a tank of about 225 to 340 L would be the starting point, and many owners choose a larger standard tank for convenience.

Why is the underground tank bigger than the overhead tank?

The underground tank is the buffer against supply interruptions, so it holds a day or more of water. The overhead tank only has to feed the taps between pump cycles.

Does the fire water tank count in this calculation?

No. The firefighting reserve is a separate requirement set by the fire code, and it should not be counted as part of the domestic storage.

How many hours should the pump run?

It depends on the design. A pump that runs for a few hours a day keeps wear and energy cost reasonable. A shorter time means a higher flow and a bigger pump, and a longer time means a smaller pump that runs for more hours.

Is a calculator enough for the final design?

A calculator is good for a first estimate. The final design should be checked against the applicable code, the supply conditions and the approval of a qualified plumbing or public health engineer.

Note: This guide is for learning and estimation. The lpcd figures, allowances and storage proportions in the examples are typical and illustrative. Always verify the final design against the applicable standards (for example the National Building Code and IS codes), the local authority’s requirements and a qualified engineer. See the full Disclaimer.
A note from MEP Analysis: Before you fix any tank size, write down three things on one line: the population you designed for, the lpcd figure you used, and the days of storage you chose. If a tank later turns out to be too small, this one line shows immediately which of the three assumptions was off, and that is much faster than rechecking the whole calculation.

Try it yourself

Enter your own population and water use in the calculator and compare the result with the hand calculations above.

🚿 Open the Daily Water Demand Calculator