An air conditioner’s size is quoted in tons, but the air it moves is measured in CFM, and designers need both numbers. The tonnage tells you how much heat the unit can remove. The airflow tells you how big the fan, the grilles and the ducts must be. If the airflow is too low, the coil gets too cold and the room is poorly cooled. If it is too high, the air is noisy and the ducts are oversized. This guide explains how TR and CFM are linked, shows the formula behind the well-known “400 CFM per ton” rule, and works through three examples you can repeat by hand.
What CFM means
CFM stands for cubic feet per minute. It is the volume of air that passes a point every minute. You will meet it on fan and AC data sheets, in duct design and in ventilation requirements. In metric units the same flow appears as m³/h, m³/s or L/s.
| To convert | Multiply by |
|---|---|
| CFM to m³/h | 1.699 |
| CFM to L/s | 0.4719 |
| CFM to m³/s | 0.000472 |
| m³/h to CFM | 0.5886 |
| m³/s to CFM | 2,118.9 |
If you need other conversions, the MEP Unit Converter covers airflow, pressure and capacity units together.
Why the heat load is split into two parts
An air conditioner removes two kinds of heat from a room, and only one of them is linked to the temperature of the air.
| Type of heat | What it does | Where it comes from |
|---|---|---|
| Sensible heat | Changes the air temperature, the thing a thermometer shows. | Sun through walls and glass, lights, equipment, people’s body heat. |
| Latent heat | Removes moisture from the air without changing its temperature. | People breathing and perspiring, cooking, outside air carrying humidity. |
The airflow is worked out from the sensible part only, because it is the temperature drop across the coil that the air has to carry. The share of sensible heat in the total is called the sensible heat ratio (SHR).
For comfort cooling, an SHR of around 0.7 to 0.8 is often assumed. A crowded room in a humid climate has a lower SHR, because there is more moisture to remove. The real figure should come from the load calculation or the equipment data.
The airflow formula
The number 1.08 is not magic. It comes from the properties of standard air near sea level:
ΔT is the difference between the air entering the coil (the return air) and the air leaving it (the supply air). A typical value for comfort cooling is about 20 °F, though the real figure depends on the equipment and the design. A wider ΔT needs less air, and a narrower one needs more.
The metric version of the same formula is:
Here 1.2 kg/m³ is the density of air and 1.006 kJ/kg·°C is its specific heat. Both formulas are for standard air near sea level. At high altitude the air is thinner, so the same load needs a larger volume of air.
Where the 400 CFM per ton rule comes from
One ton of cooling is 12,000 BTU/h. With an SHR of 0.75, the sensible part is 12,000 × 0.75 = 9,000 BTU/h. Now use a temperature difference of 20 °F:
So the rule of thumb of about 400 CFM per ton is simply this formula with typical values already filled in. Because it assumes an SHR and a ΔT, it is a quick check, not a design value. Here it is applied to common sizes:
| Capacity | BTU/h | Rough airflow at 400 CFM per ton |
|---|---|---|
| 1 TR | 12,000 | about 400 CFM |
| 1.5 TR | 18,000 | about 600 CFM |
| 2 TR | 24,000 | about 800 CFM |
| 3 TR | 36,000 | about 1,200 CFM |
| 5 TR | 60,000 | about 2,000 CFM |
Worked example 1: TR to CFM
A room is cooled by a 1.5 TR air conditioner. Find the airflow, assuming an SHR of 0.75 and a ΔT of 20 °F. These are illustrative values for learning.
Sensible heat = 18,000 × 0.75 = 13,500 BTU/h
CFM = 13,500 ÷ (1.08 × 20) = 13,500 ÷ 21.6 = 625 CFM
| Airflow | Value |
|---|---|
| In CFM | 625 |
| In m³/h | 625 × 1.699 ≈ 1,062 |
| In L/s | 625 × 0.4719 ≈ 295 |
| Per ton | 625 ÷ 1.5 ≈ 417 CFM per TR |
You can check your own numbers with the TR to CFM and CFM to TR Calculator.
Worked example 2: CFM to TR
A ducted fan coil unit is rated for 800 CFM of supply air at a ΔT of 20 °F. What cooling capacity does that airflow support, again with an SHR of 0.75?
Total load = 17,280 ÷ 0.75 = 23,040 BTU/h
Tons = 23,040 ÷ 12,000 = 1.92 TR
What changes if ΔT or SHR changes
The 400 CFM per ton rule hides two assumptions. Here is what happens to the 1.5 TR example when each one changes:
| Case | Calculation | Airflow |
|---|---|---|
| Base: ΔT 20 °F, SHR 0.75 | 13,500 ÷ (1.08 × 20) | 625 CFM |
| Narrower ΔT of 15 °F | 13,500 ÷ (1.08 × 15) | 833 CFM |
| Wider ΔT of 25 °F | 13,500 ÷ (1.08 × 25) | 500 CFM |
| Lower SHR of 0.65 (humid room) | 11,700 ÷ (1.08 × 20) | 542 CFM |
| Higher SHR of 0.85 (dry room) | 15,300 ÷ (1.08 × 20) | 708 CFM |
Worked example 3: sizing the main duct
A ducted system with a 3 TR unit supplies cold air through one main duct. Find the airflow and the duct area for a chosen velocity.
Sensible heat = 36,000 × 0.75 = 27,000 BTU/h
CFM = 27,000 ÷ (1.08 × 20) = 1,250 CFM
The area of the duct depends on the air velocity you choose, in feet per minute (fpm):
Round duct diameter = √(4 × area ÷ π)
| Velocity | Area | Round duct diameter | Same area as a rectangle |
|---|---|---|---|
| 800 fpm | 1.56 ft² (225 in²) | about 17 in | for example 20 in × 11 in |
| 1,000 fpm | 1.25 ft² (180 in²) | about 15 in | for example 18 in × 10 in |
| 1,200 fpm | 1.04 ft² (150 in²) | about 14 in | for example 15 in × 10 in |
The rectangular sizes in the last column have the same cross-section area as the round duct, which is enough for this quick check. For the real friction loss, a rectangular duct is converted to an equivalent round size using standard charts or a duct calculator, and those two sizes are not the same number.
Fresh air is a separate requirement
The airflow above is the air that circulates through the coil. A building also needs outside air for ventilation, and the amount depends on the number of people and the area of the space. The values are set by the applicable code or standard, such as ASHRAE 62.1, the ISHRAE guidelines or the National Building Code, so take them from the edition that applies to your project. The outside air adds to the cooling load, and it is part of the total airflow that the system has to handle.
Common mistakes
- Treating 400 CFM per ton as exact. It is a rule of thumb with an assumed SHR and ΔT built into it.
- Using the total load instead of the sensible load in the CFM formula.
- Mixing °C and °F in the 1.08 formula. The constant 1.08 is for ΔT in °F.
- Ignoring altitude. The formulas above are for standard air near sea level.
- Choosing a very high duct velocity to save space, then dealing with noise and a bigger fan.
- Comparing m³/h with CFM without converting. A flow of 1,000 m³/h is only about 589 CFM.
- Forgetting outside air when summing the airflow and the load of the system.
Quick checklist
- Total cooling load found in BTU/h or TR
- SHR taken from the load calculation or the equipment data
- ΔT chosen from the equipment data, not just assumed
- CFM calculated and compared with the 400 CFM per ton rule as a sanity check
- Duct area worked out from a sensible velocity
- Outside air requirement checked against the code
Frequently asked questions
How many CFM does a 1 ton AC need?
About 400 CFM is the usual rule of thumb. The exact figure depends on the SHR and the temperature difference, and it can range from roughly 350 to 450 CFM per ton or more.
How do I convert TR to CFM?
Multiply the tons by 12,000 to get BTU/h, multiply by the SHR to get the sensible heat, and divide by 1.08 times ΔT in °F. For a quick estimate, multiply the tons by 400.
What is the 1.08 in the CFM formula?
It is the product of 60 minutes per hour, the density of standard air (0.075 lb/ft³) and the specific heat of air (0.24 BTU/lb·°F). It applies to standard air near sea level.
Why does a smaller ΔT need more airflow?
The air carries the heat away. If each cubic foot of air picks up less heat, more air is needed to carry the same load.
Is the CFM printed on a split AC the same as the calculated one?
The label or data sheet gives the rated airflow of that unit, and that is the number to use for the actual equipment. The formula here helps you check whether the airflow suits the load.
Is a calculator enough for duct design?
A calculator is good for a first estimate. The final duct design needs friction loss, fittings, fan selection and balancing, and it should be done by a qualified HVAC engineer using the applicable standards.
Try it yourself
Enter your own capacity, ΔT and SHR in the calculator and compare the result with the hand calculations above. If you are still choosing the size of the unit itself, start with our AC tonnage guide.