TR to CFM: How Much Airflow Does an AC Need? Formula and Worked Examples

An air conditioner’s size is quoted in tons, but the air it moves is measured in CFM, and designers need both numbers. The tonnage tells you how much heat the unit can remove. The airflow tells you how big the fan, the grilles and the ducts must be. If the airflow is too low, the coil gets too cold and the room is poorly cooled. If it is too high, the air is noisy and the ducts are oversized. This guide explains how TR and CFM are linked, shows the formula behind the well-known “400 CFM per ton” rule, and works through three examples you can repeat by hand.

The short answer: as a quick rule of thumb, an air conditioner needs about 400 CFM of air per ton (TR). The proper formula is CFM = sensible heat load (BTU/h) ÷ (1.08 × temperature difference in °F). The temperature difference is the gap between the room air returning to the unit and the cold air leaving it, and it is usually about 20 °F (roughly 11 °C) for comfort cooling.

What CFM means

CFM stands for cubic feet per minute. It is the volume of air that passes a point every minute. You will meet it on fan and AC data sheets, in duct design and in ventilation requirements. In metric units the same flow appears as m³/h, m³/s or L/s.

To convert Multiply by
CFM to m³/h 1.699
CFM to L/s 0.4719
CFM to m³/s 0.000472
m³/h to CFM 0.5886
m³/s to CFM 2,118.9

If you need other conversions, the MEP Unit Converter covers airflow, pressure and capacity units together.

Why the heat load is split into two parts

An air conditioner removes two kinds of heat from a room, and only one of them is linked to the temperature of the air.

Type of heat What it does Where it comes from
Sensible heat Changes the air temperature, the thing a thermometer shows. Sun through walls and glass, lights, equipment, people’s body heat.
Latent heat Removes moisture from the air without changing its temperature. People breathing and perspiring, cooking, outside air carrying humidity.

The airflow is worked out from the sensible part only, because it is the temperature drop across the coil that the air has to carry. The share of sensible heat in the total is called the sensible heat ratio (SHR).

Sensible heat = total cooling load × SHR

For comfort cooling, an SHR of around 0.7 to 0.8 is often assumed. A crowded room in a humid climate has a lower SHR, because there is more moisture to remove. The real figure should come from the load calculation or the equipment data.

The airflow formula

CFM = sensible heat (BTU/h) ÷ (1.08 × ΔT in °F)

The number 1.08 is not magic. It comes from the properties of standard air near sea level:

1.08 = 60 minutes per hour × 0.075 lb/ft³ (air density) × 0.24 BTU/lb·°F (specific heat of air)

ΔT is the difference between the air entering the coil (the return air) and the air leaving it (the supply air). A typical value for comfort cooling is about 20 °F, though the real figure depends on the equipment and the design. A wider ΔT needs less air, and a narrower one needs more.

The metric version of the same formula is:

Airflow (m³/s) = sensible heat (kW) ÷ (1.2 × 1.006 × ΔT in °C)

Here 1.2 kg/m³ is the density of air and 1.006 kJ/kg·°C is its specific heat. Both formulas are for standard air near sea level. At high altitude the air is thinner, so the same load needs a larger volume of air.

Where the 400 CFM per ton rule comes from

One ton of cooling is 12,000 BTU/h. With an SHR of 0.75, the sensible part is 12,000 × 0.75 = 9,000 BTU/h. Now use a temperature difference of 20 °F:

CFM per ton = 9,000 ÷ (1.08 × 20) = 9,000 ÷ 21.6 ≈ 417

So the rule of thumb of about 400 CFM per ton is simply this formula with typical values already filled in. Because it assumes an SHR and a ΔT, it is a quick check, not a design value. Here it is applied to common sizes:

Capacity BTU/h Rough airflow at 400 CFM per ton
1 TR 12,000 about 400 CFM
1.5 TR 18,000 about 600 CFM
2 TR 24,000 about 800 CFM
3 TR 36,000 about 1,200 CFM
5 TR 60,000 about 2,000 CFM

Worked example 1: TR to CFM

A room is cooled by a 1.5 TR air conditioner. Find the airflow, assuming an SHR of 0.75 and a ΔT of 20 °F. These are illustrative values for learning.

Total load = 1.5 × 12,000 = 18,000 BTU/h
Sensible heat = 18,000 × 0.75 = 13,500 BTU/h
CFM = 13,500 ÷ (1.08 × 20) = 13,500 ÷ 21.6 = 625 CFM
Airflow Value
In CFM 625
In m³/h 625 × 1.699 ≈ 1,062
In L/s 625 × 0.4719 ≈ 295
Per ton 625 ÷ 1.5 ≈ 417 CFM per TR
Result: a 1.5 TR unit needs about 625 CFM (about 1,060 m³/h). The quick rule of 400 CFM per ton gives 600 CFM, so the two methods agree within about 4%.

You can check your own numbers with the TR to CFM and CFM to TR Calculator.

Worked example 2: CFM to TR

A ducted fan coil unit is rated for 800 CFM of supply air at a ΔT of 20 °F. What cooling capacity does that airflow support, again with an SHR of 0.75?

Sensible heat = 1.08 × 800 × 20 = 17,280 BTU/h
Total load = 17,280 ÷ 0.75 = 23,040 BTU/h
Tons = 23,040 ÷ 12,000 = 1.92 TR
Result: 800 CFM supports about 1.92 TR, which is a 2 TR class unit. This matches the rule-of-thumb table above, where 2 TR needs about 800 CFM.

What changes if ΔT or SHR changes

The 400 CFM per ton rule hides two assumptions. Here is what happens to the 1.5 TR example when each one changes:

Case Calculation Airflow
Base: ΔT 20 °F, SHR 0.75 13,500 ÷ (1.08 × 20) 625 CFM
Narrower ΔT of 15 °F 13,500 ÷ (1.08 × 15) 833 CFM
Wider ΔT of 25 °F 13,500 ÷ (1.08 × 25) 500 CFM
Lower SHR of 0.65 (humid room) 11,700 ÷ (1.08 × 20) 542 CFM
Higher SHR of 0.85 (dry room) 15,300 ÷ (1.08 × 20) 708 CFM
What this shows: for the same 1.5 TR unit, the airflow ranges from 500 to 833 CFM, a difference of about 67%, just by changing ΔT. That is why 400 CFM per ton is a starting point for a quick check, and the real design value comes from the equipment data and the load calculation.

Worked example 3: sizing the main duct

A ducted system with a 3 TR unit supplies cold air through one main duct. Find the airflow and the duct area for a chosen velocity.

Total load = 3 × 12,000 = 36,000 BTU/h
Sensible heat = 36,000 × 0.75 = 27,000 BTU/h
CFM = 27,000 ÷ (1.08 × 20) = 1,250 CFM

The area of the duct depends on the air velocity you choose, in feet per minute (fpm):

Duct area (ft²) = CFM ÷ velocity (fpm)
Round duct diameter = √(4 × area ÷ π)
Velocity Area Round duct diameter Same area as a rectangle
800 fpm 1.56 ft² (225 in²) about 17 in for example 20 in × 11 in
1,000 fpm 1.25 ft² (180 in²) about 15 in for example 18 in × 10 in
1,200 fpm 1.04 ft² (150 in²) about 14 in for example 15 in × 10 in
Result: the 3 TR unit moves about 1,250 CFM. At 1,000 fpm the main duct needs about 1.25 ft², which is a 15 in round duct. A faster velocity makes the duct smaller, but it also adds noise and friction, which the fan then has to overcome. Designers usually choose lower velocities in quiet spaces such as bedrooms and offices, and the right limits depend on your project specification.

The rectangular sizes in the last column have the same cross-section area as the round duct, which is enough for this quick check. For the real friction loss, a rectangular duct is converted to an equivalent round size using standard charts or a duct calculator, and those two sizes are not the same number.

Fresh air is a separate requirement

The airflow above is the air that circulates through the coil. A building also needs outside air for ventilation, and the amount depends on the number of people and the area of the space. The values are set by the applicable code or standard, such as ASHRAE 62.1, the ISHRAE guidelines or the National Building Code, so take them from the edition that applies to your project. The outside air adds to the cooling load, and it is part of the total airflow that the system has to handle.

Common mistakes

  • Treating 400 CFM per ton as exact. It is a rule of thumb with an assumed SHR and ΔT built into it.
  • Using the total load instead of the sensible load in the CFM formula.
  • Mixing °C and °F in the 1.08 formula. The constant 1.08 is for ΔT in °F.
  • Ignoring altitude. The formulas above are for standard air near sea level.
  • Choosing a very high duct velocity to save space, then dealing with noise and a bigger fan.
  • Comparing m³/h with CFM without converting. A flow of 1,000 m³/h is only about 589 CFM.
  • Forgetting outside air when summing the airflow and the load of the system.

Quick checklist

  • Total cooling load found in BTU/h or TR
  • SHR taken from the load calculation or the equipment data
  • ΔT chosen from the equipment data, not just assumed
  • CFM calculated and compared with the 400 CFM per ton rule as a sanity check
  • Duct area worked out from a sensible velocity
  • Outside air requirement checked against the code

Frequently asked questions

How many CFM does a 1 ton AC need?

About 400 CFM is the usual rule of thumb. The exact figure depends on the SHR and the temperature difference, and it can range from roughly 350 to 450 CFM per ton or more.

How do I convert TR to CFM?

Multiply the tons by 12,000 to get BTU/h, multiply by the SHR to get the sensible heat, and divide by 1.08 times ΔT in °F. For a quick estimate, multiply the tons by 400.

What is the 1.08 in the CFM formula?

It is the product of 60 minutes per hour, the density of standard air (0.075 lb/ft³) and the specific heat of air (0.24 BTU/lb·°F). It applies to standard air near sea level.

Why does a smaller ΔT need more airflow?

The air carries the heat away. If each cubic foot of air picks up less heat, more air is needed to carry the same load.

Is the CFM printed on a split AC the same as the calculated one?

The label or data sheet gives the rated airflow of that unit, and that is the number to use for the actual equipment. The formula here helps you check whether the airflow suits the load.

Is a calculator enough for duct design?

A calculator is good for a first estimate. The final duct design needs friction loss, fittings, fan selection and balancing, and it should be done by a qualified HVAC engineer using the applicable standards.

Note: This guide is for learning and estimation. The SHR, ΔT and velocity values in the examples are typical and illustrative. Always verify the final design against the equipment manufacturer’s data, the applicable standards and a qualified HVAC engineer. See the full Disclaimer.
A note from MEP Analysis: When you check the airflow of an AC, write down three things next to the CFM number: the total capacity it belongs to, the ΔT, and the unit (CFM or m³/h). A bare number such as “1,000” can mean very different airflows in different units, and a short label avoids the mistake before it reaches a drawing.

Try it yourself

Enter your own capacity, ΔT and SHR in the calculator and compare the result with the hand calculations above. If you are still choosing the size of the unit itself, start with our AC tonnage guide.

💨 Open the TR to CFM Calculator