kW vs kVA vs Amps: Difference, Formulas and Worked Examples

Almost every electrical nameplate, generator brochure and electricity bill uses three terms that look similar and mean different things: kW, kVA and amps. The kW vs kVA question causes real mistakes, such as a generator that is too small, a cable that runs hot, or a feeder that trips on a load that looked fine on paper. This guide explains each term in plain words, shows the formulas that connect them, and works through four examples you can repeat by hand.

The short answer: kW is the power that does useful work. kVA is the total power the supply has to deliver. Amps is the current that flows to deliver it. The power factor (PF) links kW and kVA: kW = kVA × PF. Equipment such as cables, breakers, transformers and generators is limited by current, so it must be sized on kVA and amps, not on kW alone.

The three powers in plain words

A simple way to picture it: think of a delivery van with a fixed carrying capacity. The goods that actually reach the customer are the kW. Some trips are spent moving things back and forth without delivering anything, and that is the kVAR. The van still has to be big enough for everything it carries, and that total is the kVA.

Term Name What it means Unit
kW Real (active) power Power converted into useful work: shaft power, heat, light. kilowatt
kVA Apparent power Total power the source must supply, which is voltage times current. kilovolt-ampere
kVAR Reactive power Power that moves back and forth to build magnetic fields in motors and transformers. It does no useful work. kilovolt-ampere reactive
Amps Current The flow of charge that cables, breakers and windings must carry. ampere (A)
PF Power factor The share of kVA that becomes kW. It is a number between 0 and 1. no unit

The power triangle

kW, kVAR and kVA do not add up in a straight line. They form a right-angled triangle, with kW and kVAR as the two shorter sides and kVA as the longest side.

kVA² = kW² + kVAR²

The angle between kW and kVA is called φ (phi), and the power factor is the cosine of that angle. From this triangle you get every formula you need:

kW = kVA × PF
kVA = kW ÷ PF
PF = kW ÷ kVA
kVAR = √(kVA² − kW²)

Because the longest side of a right triangle is always at least as long as the others, kVA is never smaller than kW. They are equal only when the power factor is 1.

Formulas that connect power to amps

Voltage is the third quantity that ties everything together. Use V as the supply voltage in volts. For a three-phase supply, use the line-to-line voltage.

Supply From kVA From kW
Single-phase I = kVA × 1000 ÷ V I = kW × 1000 ÷ (V × PF)
Three-phase I = kVA × 1000 ÷ (√3 × V) I = kW × 1000 ÷ (√3 × V × PF)

The pattern is worth remembering: for the same kW, a lower power factor means more amps. That one idea explains why power factor matters so much in the rest of this guide. If you want to convert quickly, the Amps to kW Calculator and the VA to Watts Calculator do the arithmetic for you.

Typical power factor values

The values below are rough, commonly seen figures for orientation only. The real value is on the equipment nameplate or the manufacturer’s data sheet.

Type of load Typical power factor
Heater, geyser, incandescent lamp (purely resistive) Close to 1.0
Induction motor running near full load Roughly 0.8 to 0.9
Induction motor running lightly loaded Much lower, often below 0.6
Fluorescent lighting with older magnetic ballast Low, unless corrected
Modern LED drivers and computer power supplies Varies widely by design

Worked example 1: a single-phase load

A single-phase load draws 10 A from a 230 V supply at a power factor of 0.8.

kVA = 230 × 10 ÷ 1000 = 2.3 kVA
kW = 2.3 × 0.8 = 1.84 kW
kVAR = √(2.3² − 1.84²) = √1.9044 = 1.38 kVAR
Result: the supply delivers 2.3 kVA, of which 1.84 kW is useful power and 1.38 kVAR is reactive power.

Worked example 2: a three-phase motor load

A workshop has a balanced three-phase load of 50 kW at 415 V. Let us see how the power factor changes the current.

At PF 0.80:
kVA = 50 ÷ 0.80 = 62.5 kVA
I = 62.5 × 1000 ÷ (1.732 × 415) ≈ 87 A

At PF 0.95:
kVA = 50 ÷ 0.95 ≈ 52.6 kVA
I = 52.6 × 1000 ÷ (1.732 × 415) ≈ 73 A

Result: the useful power is the same 50 kW, but improving the power factor from 0.80 to 0.95 cuts the current from about 87 A to about 73 A, a drop of roughly 16%. Less current means cooler cables, lower losses and more spare capacity in the supply.

Worked example 3: how much correction does the motor load need?

Take the same 50 kW load and improve the power factor from 0.80 to 0.95 with capacitors. The capacitors supply the reactive power, so the supply no longer has to.

kVAR before = √(62.5² − 50²) = 37.5 kVAR
kVAR after = √(52.6² − 50²) ≈ 16.4 kVAR
Capacitor needed = 37.5 − 16.4 ≈ 21 kVAR

So a capacitor bank of about 21 kVAR is needed. In practice you choose the nearest standard rating and, for loads that change, an automatic bank. The Capacitor Bank Calculator works this out from your own kW and power factor values.

Worked example 4: sizing a generator in kVA

Diesel generator sets are usually rated in kVA at a power factor of 0.8, so a set’s kW output is its kVA rating multiplied by 0.8. Suppose the connected running load is 40 kW.

kVA needed = 40 ÷ 0.8 = 50 kVA
With a 25% margin = 50 × 1.25 = 62.5 kVA

Pick the next standard rating offered by the manufacturer. As a check, a 62.5 kVA set at 0.8 PF can deliver 62.5 × 0.8 = 50 kW, which covers the 40 kW load with margin. The margin is a design decision, and motor starting current needs a separate check, because starting a large motor can draw several times its running current.

Why kVA matters more than kW for equipment sizing

Heat in a cable or in the windings of a generator or transformer is caused by current, and current depends on kVA. A transformer feeding a low power factor load can reach its current limit while delivering far less than its kW rating. That is why transformers, generators and UPS systems carry a kVA (or VA) rating instead of a kW rating.

Power factor Real power delivered by a 100 kVA source
1.00 100 kW
0.95 95 kW
0.90 90 kW
0.80 80 kW
0.70 70 kW

The same source can supply 30 kW less useful power when the power factor falls from 1.00 to 0.70. Once the amps are known, the next step is to choose a cable for them, which is covered step by step in our cable size selection guide.

Do kW and kVA matter for your electricity bill?

It depends on the tariff. Ordinary household meters record energy in kWh, so the bill follows real power. Many commercial and industrial connections have tariffs or penalties linked to kVA demand, kVAh or power factor. Check the tariff order of your own electricity distribution company for the exact rule that applies to you.

Common mistakes

  • Treating kW and kVA as the same. They are equal only at a power factor of 1.
  • Sizing a generator or UPS on kW alone and ignoring the power factor.
  • Using the single-phase formula for a three-phase load, or forgetting the √3 factor.
  • Assuming one power factor for everything. A lightly loaded motor has a much lower power factor than the same motor at full load.
  • Using phase voltage instead of line voltage in the three-phase formula.
  • Adding kW and kVAR directly. They combine as the sides of a right-angled triangle, not by simple addition.
  • Ignoring starting current when choosing a generator for motor loads.

Quick checklist

  • Know whether the rating you have is in kW, kVA or amps, and at what power factor
  • Use the right formula for single-phase or three-phase supply
  • Size cables, breakers, transformers and generators on kVA and amps
  • Check the nameplate for the real power factor instead of assuming one
  • Add a sensible margin and check motor starting separately

Frequently asked questions

Is kVA always bigger than kW?

Kva is bigger than or equal to kW. Power factor cannot be more than 1, so kW = kVA × PF can never exceed the kVA value.

Why are generators and transformers rated in kVA?

Their limit is the current they can carry safely, and current does not depend on the power factor of the load. The kVA rating describes that limit no matter what load is connected.

What is the difference between kW and kWh?

kW is the rate at which power is used at a moment. kWh is the energy used over time. A 2 kW heater running for 3 hours uses 6 kWh.

How do I convert kVA to kW?

Multiply kVA by the power factor. For example, 62.5 kVA at a power factor of 0.8 is 50 kW. To go the other way, divide kW by the power factor.

What happens if the power factor is low?

The same useful power needs more current. That means heavier cables, higher losses, more voltage drop and less spare capacity in the transformer or generator.

What power factor should I assume if I do not know it?

Do not guess for a final design. Read it from the nameplate or data sheet. For a rough early estimate, designers often assume a value such as 0.8 for mixed motor loads, but this must be confirmed later.

Note: This guide is for learning and estimation. Power factor values and ratings in the examples are illustrative. Always verify the final design against the applicable standards, the manufacturer’s data and a qualified engineer. See the full Disclaimer.
A note from MEP Analysis: Whenever you copy a rating from a nameplate or a quotation, write the unit and the power factor next to the number. A figure that says only “50” can mean 50 kW or 50 kVA, and the two give very different currents. Taking five seconds to label it is the cheapest way to avoid an undersized cable or generator.